2 on-board touchpad and sk-5235 operation, 1 view control panel firmware number and revision, On-board touchpad and sk-5235 operation -2 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual
Page 67

Operation 151204
5-2
5.2
On-board Touchpad and SK-5235 Operation
Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table 5-1. If you are
using an annunciator key or the Flex Door option, you are not required to enter a code for operator level
functions.
If no keys are pressed for 4 minutes while in program mode, the system will time out and resume normal
operation.
* Code = any valid operator or installer code.
5.2.1
View Control Panel Firmware Number and Revision
When 0 ENTER and the code is entered The system will perform a display lamp test and a communication test.
Table 5-1: Basic Panel Operations Using the On-Board Annunciator and the SK-5235
How To
Do This
Comments
Press
Display
Message
Press*
Test the system
0 ENTER
System Test
Enter Code
Enter Code
System performs a display lamp test, a
communication test, and displays the
firmware number and revision. See 5.2.1 for
an example.
Reset Alarms
1 ENTER or RESET
Reset Alarm
Enter Code
Enter Code
Resets system.
Clear History
2 ENTER
Clear History
Enter Code
Enter Installer
Code
Clears event history of all events.
Reset the Dialer
3 ENTER
Reset Dialer
Enter Code
Enter Code
Resets the dialer and aborts the call to central
station.
Call Computer to Up/
Download
4 ENTER
Call Computer
Enter Code
Enter Installer
Code
Will dial the programmed phone number for
the computer to initiate an up or download.
Display History
Events
5 ENTER
History Events
Enter Code
Enter Code
Displays panel history, including alarms,
supervisories, troubles, reports, time and date
changes, etc.
Show Status
6 ENTER
Show Status
Enter Code
Enter Code
View existing system status. List Alarms
first, supervisories and then troubles.
Silence Troubles or
Alarms
7 ENTER or SILENCE
Silence
Enter Code
Enter Code
Set the Date
8 ENTER
Set Date
Enter Code
Enter Code
Enter 8 digits for the date. For example, to set
the date 08/31/1999 enter 08311999. Press #
to clear incorrect entries.
Set the Time
9 ENTER
Set Time
Enter Code
Enter Code
Enter the time in 24 hour increments. For
example, 1:00 pm = 13:00.
Disable/Enable a
Zone
Zone # + *
Disable Zone
Enter Code
Enter Code
Repeat the process to enable the zone.
Disable/Enable NAC
10 NAC # *
Disable NAC
Enter Code
Enter Code
Repeat the process to enable the NAC.
Conduct a Fire Drill
20 ENTER
Fire Drill
Enter Code
Enter Code
To End the Fire Drill press RESET then code.
Reset Detectors
21 ENTER
Rst Smk Pwr
Enter Code
Enter Code
Resets all smoke detector power.
Walk Test the System
22 ENTER
Walk Test
Enter Code
Enter Code
To End the Walk Test press REST.
Menu of Options
Press
or
to
scroll through list.
To exit press ENTER or wait 15 seconds.