beautypg.com

A.2 two-wire smoke detectors – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 93

background image

Model SK-5208 Installation Manual

151204

A-11

A.2

Two-Wire Smoke Detectors

The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-5217 zone
expander. The table is organized by manufacturer. The columns show the number of detectors per loop that can
be used.

Manufactu

rer

Enhanced

Mode

Compatible

Model Name or Number

(Base model name or number in

parentheses.)

Compatibility ID

# per Loop

Head

Base

Apollo

55000-150, 151, 152, 153

55000-150,
151, 152, 153

45681-200, 220, 230,
231, 232

40

3

55000-250

55000-350

45681-200, 220, 230,
231, 232

40

3

55000-350

55000-250

45681-200, 220, 230,
231, 232

25

55000-380

55000-380

45681-200, 220, 230,
231, 232

15

3

55000-225

55000-225

45681-255, 256

45681-200, 220, 230,
232, 251, 252

15 / loop for

Ion Detectors

15 / loop for

Photoelectric

detectors

3

55000-226

55000-226

3

55000-227

55000-227

3

55000-325

55000-325

3

55000-328

55000-328

3

55000-326

55000-326

3

55000-327

55000-327

Detection
Systems

DS200 (MB200-2W)

B

A

24

DS200HD (MB200-2W)

B

A

24

DS250 (MB2W or MB2WL)

B

A

18

DS250HD (MB2W or MB2WL)

B

A

18

DS250TH (MB2W or MB2WL)

B

A

18

ESL

3

425 (S10)

N/A

S00

30

3

425C (S10)

N/A

S00

30

3

425CR (S10)

N/A

S00

30

3

425CRT (S10)

N/A

S00

30

3

425CT (S10)

N/A

S00

30

3

429C (S10A)

N/A

S10A

30

3

429CRT (S11A)

N/A

S11A

30

3

429CST (S11A)

N/A

S11A

30

3

429CT (S10A)

N/A

S10A

30

3

521B

N/A

S10A/S11A

40

3

521BXT

N/A

S10A/S11A

40

3

609U01-11

S10

S00

40

3

609U02-11

S10

S00/S03

40

3

611U (601U or 602U)

S10

S00/S03

40

3

611UD (601U or 602U)

S10

S00/S03

40

3

611UT (601U or 602U)

S10

S00/S03

40

3

612U (601U or 602U)

S10

S00/S03

40

3

612UD (601U or 602U)

S10

S00/S03

40