2 nfpa 72 polarity reversal, 2 nfpa 72 polarity reversal -28 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 38

background image

Control Panel Installation 151204

3-28

3.

Program NAC #4 to be direct connect from the NAC Options menu. Relay #4 will automatically be config-
ured to indicate system troubles.

Note: It is not possible to reset the remote indication until you clear the condition and reset the SK-5208.

Figure 3-26 City Box Connection

3.15.1.2 NFPA 72 Polarity Reversal

When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote
site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the
condition is cleared and the SK-5208 panel is reset.

If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.

To install the 5220 for polarity reversal, follow the steps below:

1.

Locate the knockout on the right side of the SK-5208 cabinet to connect the 5220 using a short piece of con-
duit (must not exceed 20 feet in length).

2.

Wire the 5220 to the SK-5208 using the four-wire pigtail provided as shown in Figure 3-27 (next page). This
diagram also shows how to connect the 5220 to the remote indicator.

3.

Program one of the notification circuits to be Direct Connect (Figure 3-27 uses NAC 4 and Relay 4). The
relay and NAC circuits are paired when selected as direct connect. For example, if NAC 4 is programmed as
Direct Connect then relay 4 used for the trouble output. Do not program the NAC for Silence or Supervision
(NACs with EOL).

5220

Control

Supervised for

Opens and Ground Faults

City Box

Coil Resistance

14.5

Panel