beautypg.com

3 maximum battery standby load, 7 ac wiring, 3 maximum battery standby load -6 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 16: Ac wiring -6

background image

Control Panel Installation 151204

3-6

10% of zones in alarm, but in no case less then three zones per UL864

3.6.3

Maximum Battery Standby Load

Table 3-3 shows the maximum battery standby load for the SK-5208 based on 24 and 60 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2) must be less than the
number shown in Table 3-3 for the battery size used and standby hours required.

Batteries larger then 18 AH will not fit into the SK-5208 cabinet and must be housed in the RBB remote battery
box cabinet. See Section 3.8 for battery installation.

*

Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter
(DACT).

3.7

AC Wiring

The Model SK-5208 power supply delivers 24 VDC at 6A for smoke detector power, notification device power,
and accessory power. Figure 3-3 shows the AC connections to the SK-5208 control panel.

Figure 3-3 AC Wiring

Table 3-3: Maximum Battery Standby Load

Rechargeable Battery Size

Max. Load for 24 hrs.

Standby, 5 mins. Alarm

*Max. Load for 60 hrs.

Standby, 5 mins. Alarm

7 AH

270 mA

105 mA

12 AH

475 mA

190 mA

18 AH

685 mA

270 mA

35 AH

1.1 A

450 mA

Warning!

Silent Knight does not support the use of batteries smaller than those listed in Table 3-3. If you use a battery too small
for the installation, the system could overload the battery resulting in the installation having less than the required 24
hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for your installation.