beautypg.com

3 electrical compartment, 0 maintenance procedures (cont’d) – Reznor PDH Operation Manual PreevA User Manual

Page 8

background image

Form O-PreevA, Page 8

3.3.5 Built-in On/

Off Control Switch,

Option BA6

Function: Optional lockable service control switch.

Service: If it is determined that the control switch needs to be replaced, use only the

factory-authorized replacement part that is designed for the heater.

Location: Switch is conveniently mounted below the electrical compartment on the

outside of the unit.

Application: The switch on Models PDH, SDH, SHH, PXH, RHH, RDH, and RXH

is

P/N 205908. The switch used on Models PEH and REH differs by size; see chart

below.

3.3.3 Door

Switch -

Models

SDH, SHH

Function: Prevents unit from operating when the heat section door is open.

Service: If it is determined that the door switch needs replacing, use only a

factory-authorized replacement part that is designed for the heater.

Location: Models SDH/SHH heat section.

P/N

217262

3.0 Maintenance

Procedures

(cont’d)

OPTION BA6 REQUIRED DISCONNECT SIZE for Electric Heat MODELS PEH and REH (AMPS)

208/1/60

240/1/60

208/3/60

240/3/60

460/3/60

575/3/60

10 KW

80

100

N/A

N/A

N/A

N/A

15 KW

100

125

N/A

N/A

N/A

N/A

20 KW

125

200

80

80

60

60

30 KW

200

200

100

125

60

60

40 KW

N/A

N/A

125

200

80

60

60 KW

N/A

N/A

200

200

100

100

80 KW

N/A

N/A

200

250

125

125

90 KW

N/A

N/A

250

N/A

200

125

120 KW

N/A

N/A

N/A

N/A

200

200

Available Disconnect Switch Sizes (Amps): 60 (P/N 205906), 80 (P/N 205907),

100 (P/N 205908), 125 (P/N 207678), 200 (P/N 207679) and 250 (P/N 222422)
Note:
These ratings are based upon 115% of the total FLA for heat modules plus

motor.

3.3.1 Reverse Flow

Limit Control - PDH,

SDH, RDH, RHH, SHH

Function: The reverse flow limit control is an automatically reset, temperature acti-

vated safety control.
Service: If it is determined that the reverse flow limit control needs replacing, use only

a factory-authorized replacement part that is designed for the size of heater.
Location: PDH/SDH/RDH 75-150 in the blower section. PDH/SDH/RDH 175-400 and

all RHH/SHH in the heat section. For approximate location, see

FIGURE 1A, page 5.

3.3.2 Transformer

Service: Use a voltmeter to verify that there are 24 volts output from a

transformer. If the transformer is not functioning, it must be replaced. Use

a replacement transformer identical to the factory-installed model.

Location: See FIGURE 1A, page 5, or 1B, page 6, for location.

P/N

211754

3.3 Electrical Compartment

Check the wiring and connections. Replace any wiring that is deteriorated.

CAUTION: If any of the original wire as supplied with the appliance

must be replaced, it must be replaced with wiring material having a

temperature rating of at least 105°C, except for sensor lead wires which

must be 150°C. See Hazard Levels, page 2.

Controls identified below apply to all models unless specifically listed.

3.3.4 Condensate

Pressure Switch

- Models RHH &

SHH

Function: If the condensate drain is blocked causing the sensing pressure to

be outside the switch setpoint, the pressure switch will shutoff the gas valve.

The gas valve will remain off until the problem is corrected.
Service: If it is determined that the condensate pressure switch needs replac-

ing, use only a factory-authorized replacement part that is designed for the

heater.

Location: See FIGURE 1A, page 5, Item 22, for location.

P/N 217085