4.2 Troubleshooting - Modulating Control Module used on Model RDH Sizes 175-400,

Model RHH, or Model SHH with Gas Control Option AG58 or D12G

The control that operates the furnace has a built-in, self-diagnostic capability. The control continuously monitors its own

operation and the operation of the system. The LED on the control indicates the current state, warnings, failures, and

test modes.

Normal Furnace Operation Display

LED Display

Heat Mode

Description

OFF Mode (OFF)

System Idle - Control board has power, no faults found, no call for heat.

PURGE Mode (Pur)

System is purging the heat exchanger – No gas on, no flame, venter motor runs for the specified

purge timings. Purge cycles occur immediately before and after each burner operation.

IGNITION Mode (Ign)

System is initiating burner operation – Ignitor energized, modulating valve moved to ignition

setting, gas on. Maintained for the trial-for-ignition period and the five-second flame stabilization

period.

WARM-UP Mode

(HEA)

(Board Self Check)

Period between Ignition and Run – System checks completed before modulation control begins.

RUN Mode (run)

Normal modulating operation.

Ignition Retry (rEt)

System has had a failed ignition attempt or has lost flame during burner operation and is

beginning another ignition cycle.

3 Character LED

Display used to show

deep modulation board

codes for status, alarm,

and error information.

ID Plug

(unique by

model, heat

section size, &

type of gas)

Deep Modulation (Option AG58 and D12G) Ignition Board

is in the Control Compartment (See FIGURE 1A, page 5.)

Contactor

Signal Input

Terminals (J4)

Board Power

and Signal (J6)

Control Board

Fuse (3A)

Plug Connec-

tion for Board

Control Points

(J8)

• Ball Valve

Actuator Power,

Drive Voltage,

and Feedback

Signal
• Off Board

Digital Venter

Air Pressure

Switch and Unit

Primary Limit

Switch

On board Air Pressure Sensor for Monitoring Inducer Pressure.
Venter Sensing Tubing is connected from Venter housing to "LO"

pressure input point on air sensing transducer.

Gas Manifold PSI Transducer

Plug 3-wire (red, black, and green)

Wiring Connection (J13)

J9, J10, J3, and J2 are

not currently used.

Flame

Sensor

Spade

Connection

(T8)

Inducer

Motor

Capacitor

Spade

Connection

(AUX-L2

T6

)

Inducer Motor Main Power

Connection Spades

(IND-L2

T3

and IND-L1

T2

)

Main Board Supply Power Input

Spades (L1

T1

and L2

T5

)