beautypg.com

Reznor PDH Operation Manual PreevA User Manual

Page 26

background image

Form O-PreevA, Page 26

3.7 Optional

Cooling Coil

Module (cont’d)

Reheat Module Compressor Maintenance and Replacement (cont’d)

3.0 Maintenance

Procedures

(cont’d)

Step 11. Check Circuit Subcooling and Superheat of Reheat

Circuit

PREPARATION:

To verify superheat and subcooling, outdoor temperature must be between

70-95°F (21-35°C). If temperature is not within this range, consult the factory

service department before charging.

Operate for 30 minutes for system to stabilize.

Check SUBCOOLING of the Reheat Circuit - Measure and record temperature

and pressure of the liquid line at the condenser coil outlet in the reheat circuit.

STEP 1) Record Measurements: Temperature =

________°F (°C) and Pressure = ________ psig

STEP 2) From Temperature/Pressure Conversion Chart,

APPENDIX, page 38, convert Measured Pressure (STEP 1) to

________°F (°C)

STEP 3) Subtract Measured Temperature (STEP 1) from Temperature

from Conversion Chart (STEP 2)

________°F (°C) - ________°F (°C) = ________°F (°C) degrees

of Subcooling

Recommended reheat circuit subcooling with outdoor temperature

range of 70-95°F (21-35°C) is 14-18°F (7.8-10°C).

Too much subcooling indicates a refrigerant overcharge. To reduce the

subcooling, remove excess refrigerant. Too little subcooling indicates a refrigerant

undercharge. To increase subcooling, slowly add R410A refrigerant.

WARNING

Do not release refrigerant to the atmosphere. When adding or

removing refrigerant, the qualified technician must comply

with all national, state/province, and local laws.

Determine SUPERHEAT of the Reheat Circuit - Measure and record temperature

(insulate probe from surrounding air temperature) and pressure in the suction line

at the compressor inlet of the reheat circuit.

STEP 1) Record Measurements: Temperature =

_______°F (°C) and Pressure = _______ psig

STEP 2) From Temperature/Pressure Conversion Chart,

APPENDIX, page 38, convert Measured Pressure (STEP 1) to

________°F (°C)

STEP 3) Subtract Measured Temperature (STEP 1) from

Temperature from Conversion Table (STEP 2)

________°F (°C) - ________°F (°C) = ________°F (°C) degrees

of Superheat

Recommended reheat circuit superheat at is 8-12°F (4.5-6.7°C).

Typically, too much superheat indicates that the evaporator coil is undercharged.

Too little superheat typically indicates that the evaporator coil is overcharged and

may potentially flood liquid refrigerant to the compressor. To reduce the superheat,

adjust the thermal expansion valve by turning the adjusting stem counterclock-

wise. To increase the superheat, adjust the thermal expansion valve by turning the

adjusting stem clockwise.

Step 12. (Select the procedure that applies.)

IF the oil measured in Step 2 was significantly less than in the table on

page 21 or the acid test in

Step 2 indicated a burnout, do the following:

a) Operate the unit for several hours. Check the pressure drop through the

3.7.4 Optional Reheat

Module (cont’d)