8 optional evaporative cooling module – Reznor PDH Operation Manual PreevA User Manual

Page 27

background image

Form O-PreevA, P/N 234661R8, Page 27

temporary suction line filter drier. If the pressure drop exceeds 8 psig, recover

the refrigerant, replace the suction line filter drier with the same type as

removed, replace the liquid line filter drier, evacuate the circuit, and re-charge

with the recovered refrigerant).

Continue to monitor the pressure drop through the suction line filter drier and

repeat the process above until the pressure does not exceed 8 psig after

several hours of operation. (NOTE: System must be allowed to run no more

than 72 hours with a suction line filter drier.)

b) Allow the system to operate for 4-8 hours. Recover the refrigerant and take an

oil sample. Retest the oil for acid.

c) If the test for acid is negative, remove the suction line filter drier, replace the

liquid line drier, evacuate, and re-charge the system with the recovered refriger-

ant.

If the test indicates acid, replace both the liquid line filter drier and the suction

line filter drier and repeat b) and c).

CAUTION: After cleanup is complete, remove the suction

line filter drier. See Hazard Levels, page 2.

d) Verify subcooling and superheat (refer to

Step 11).

e) When the system is operating properly, remove the gauges.

IF the oil measured in Step 2 was not significantly less than that shown

in the table on page 21 or the acid test in

Step 2 did not indicate a

compressor burnout, continue to the review in

Step 13.

Step 13 . Review ALL Steps to ensure that nothing was

overlooked.

3.7.5 Modulating

Reheat Control

(Option AUR1)

Function: Units with modulating reheat control (Option AUR1) have a temperature

control board with a potentiometer, an air temperature sensor, and an electric dis-

charge bypass valve. When reheat is active, the sensor monitors the air temperature

as it leaves the reheat coil. Based on the potentiometer setpoint, the board will open

or close the bypass valve. If the leaving air temperature is higher than the setpoint, the

board will open the valve adding refrigerant hot gas to the refrigerant liquid before it

enters the pre-cool coil. This reduces the coil's ability to absorb the heat, and thus, the

reheat coil's ability to reject. If the leaving air temperature is lower than the setpoint,

the opposite occurs.
Service: Check the wiring connections at the board. The board is polarity sensitive;

positive connects to terminal 1 and negative to terminal 2.
The valve may be tested by measuring the resistance of the leads. Remove the power

and the leads from the board before testing. Resistance between the black and white

leads should be about 75 Ohms. Resistance between the green and red leads should

be within 5% of the white and black.
Use only factory-authorized replacement parts.

3.8 Optional

Evaporative

Cooling Module

Media

Media

Media

Media

Airflow

Door Panel

When equipped with an

evaporative cooling module,

the evaporative cooling

module is always the first

module in system. Air enters

the system through the

evaporative cooling media.
See the heater installation

manual for additional

information about the

operation of the evaporative

cooling module.