beautypg.com

Reznor PDH Operation Manual PreevA User Manual

Page 37

background image

Form O-PreevA, P/N 234661R8, Page 37

F. Noisy unit

operation.

1. Blower rotational noise.

1. Check blower, motor and drive for faulty adjustment or noisy bearings, loose parts,

and/or blower out of balance.

2. Air noise.

2. Check ductwork. Air velocity too high.

3. Chattering contactor.

3. Check for adequate control voltage, check for shorts or breaks, check thermostat,

check contact points.

4. Tubing rattle.

4. Dampen by taping or clamping, carefully bend tubing away from contact when

possible.

G. High

suction

pressure

1. Excessive load on evaporator coil.

1. Check superheat; see condensing unit manual or Paragraph 3.7.4, Step 11. Check

for high entering wet bulb temperature. Check for excessive air.

2. Compressor is unloaded.

2. Check head pressure. Check thermal expansion valve. If valve is not functioning

properly, check pressure drop across filter drier.

3. Expansion valve not secured to suction

line or defective.

3. Check the thermal expansion valve; ensure bulb is attached properly and insulated.

H. High

discharge

pressure.

1. Refrigerant overcharge.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Adjust

refrigerant charge.

2. Thermal expansion valve setting.

2. Check superheat; see condensing unit manual or Paragraph 3.7.4, Step 11. Adjust

valve as needed.

3. Air inlet to condenser dirty or

obstructed.

3. Check for proper clearances and possible air recirculating.

4. Condenser fan motor defective.

4. Check condenser fan motor and capacitor.

I. Suction

pressure is too

low.

1. Refrigerant undercharge.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Add

refrigerant as needed.

2. Thermal expansion valve setting.

2. Check superheat; see condensing unit manual or Paragraph 3.7.4, Step 11. Adjust

valve as needed.

3. Blower running backward.

3. Interchange any two wires from 3 phase disconnect.

4. Loose blower, pulley or belts.

4. Check drive pulley alignment, belt tension.

5. Defective or improperly adjusted

expansion valve.

5. Check superheat and adjust thermal expansion valve.

6. Dirty filter.

6. Check filter and evaporator coil.

7. Too little airflow or low entering air

temperature.

7. Check airflow and entering air wet bulb conditions.

8. Restriction in suction or liquid line.

8. Check refrigerant circuit for restriction.

J. Head

pressure too

low.

1. Insufficient refrigerant charge.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Check

for leak. Repair; add refrigerant.

2. Defective or improperly adjusted

expansion valve.

2. Check superheat; see condensing unit manual or Paragraph 3.7.4, Step 11. Adjust

thermal expansion valve.

3. Low suction pressure.

3. See “I. Suction pressure too low” above.

4. Defective compressor.

4. See “G. High suction pressure” above.

K. Compressor

short cycles.

1. Improper refrigerant charge.

1. Check subcooling and superheat; see condensing unit manual or Paragraph 3.7.4,

Step 11.

.

2. Defective high or low pressure control. 2. Check high or low pressure switch.

3. Liquid floodback.

3. Possible tight bearings, see above.

4. Defective expansion valve.

4. Check superheat and thermal expansion valve.

5. Poor air distribution.

5. Check ductwork for recirculating.

6. High discharge pressure.

6. See “H. High discharge pressure” above.

7. Leaking discharge valves in

compressor.

7. See “G. High suction pressure” above.

L. Running

cycle is too

long or unit

operates

continuously.

1. Refrigeration undercharged.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Add

refrigerant.

2. Dirty filter or evaporator coil.

2. Check filter, coil, and airflow.

3. Dirty or clogged condenser coil.

3. Check coil and airflow.

4. Air or other non-condensables in

system.

4. Check equalized high side pressure with equivalent outdoor temperature.

5. Defective compressor.

5. See “high suction pressure” above.

6. Restriction in suction and liquid line.

6. Check for restrictions in refrigerant circuit.

7. Control contacts stuck.

7. Check wiring.

M. Supply air

temperature is

too high.

1. Refrigerant undercharge or leak in

system.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Check

for leaks.

2. Evaporator plugged with dirt or ice.

2. Check evaporator, airflow, and filter.

3. Improperly adjusted or defective

expansion valve.

3. Check superheat & adjust thermal expansion valve, check bulb.

4. Defective compressor.

4. Check compressor for proper operation.

5. High discharge pressure.

5. See “high discharge pressure” above.

6. Airflow is too high.

6. Check external static pressure.

N. Supply air

temperature is

too low.

1. Airflow is too low.

1. Check evaporator coil; check filters, check for closed dampers or grills, check drive

for loose parts, belts, or misalignment; check external static pressure.

2. Return air temperature too low.

2. Check entering air wet bulb conditions.

O. Liquid line

is too hot.

1. Refrigerant undercharge.

1. Check subcooling; see condensing unit manual or Paragraph 3.7.4, Step 11. Adjust

refrigerant.

2. High discharge pressure.

2. See H. above.