beautypg.com

6 dampers and controls – Reznor PDH Operation Manual PreevA User Manual

Page 19

background image

Form O-PreevA, P/N 234661R8, Page 19

3.5.1 Electric Heating

Elements

Service: Check the heating elements at the

beginning of the heating season. Carefully clean

all dust and dirt from the heating elements using

a brush or steel wool. With a vacuum or air hose,

clean the inside of the cabinet especially the bot-

tom and sides where dirt and dust will accumu-

late.
If a replacement is needed, order a complete

heat section assembly (5kw single phase or 10kw

three phase).

Single Heating Element

(Each heat section includes

an assembly of single

elements.)

Location: See the control location illustration in FIGURE 1B and 1C, pages 6 and 7.
Service: The electric heat section has a transformer, relay, digital controller, contac-

tors, fuses, and a distribution block.
Quantities and types of fuses and contactors depend on the size of unit.
If the electric heat section has SCR control (Option D12D), the controller(s) with heat-

sink are positioned as shown in

FIGURE 1C.

DANGER

High voltages are present on the terminals of the SCR power

controller(s).

If replacements are required, check with your distributor and use only factory-autho-

rized parts.

3.6 Dampers and

Controls

Reference NOTE: Codes for

electrical options are listed

on the wiring diagram.

Inlet Air Dampers

Location: Dampers and damper motors are located in either the blower section (Option

AR8) or the optional mixing box (GE Options).
Function: Dampers operate in response to the control selected. Damper controls are

shown below.
Service: Clean dampers and controls of dust and dirt.

2-Position Damper Motor (Options AR8 and GE 3, 6, 7)

Function: The 2-position damper motor opens and closes the dampers in response to

unit operation, a system switch, or a field-supplied time clock.

Motor closes dampers on heater shutdown.
Service: There is no service required on this motor other than external cleaning. If

the motor needs replaced, replace with an identical damper motor or damper motor

replacement kit.

Modulating Motor (Options GE 4, 8, 10, 11, 12, 13, 14, 15, 16, 21, 22)

Function: The modulating damper motor actuates the dampers in response to dis-

charge air temperature, building pressure, or DDC control. Some options have damper

“stops” or warmup (or cooldown) delay based on return air temperature. Motor closes

dampers on heater shutdown.
Service: There is no service required on this motor other than external cleaning. If the

motor needs replaced, replace with an identical damper motor.

Potentiometer (adjustable damper dial) (Options GE 4, 8, 10, 14)

Function: The potentiometer is a manually set switch used with modulating dampers

to set a minimum outside air damper opening. Depending on the option selected, it is

either mounted in the mixing box or remotely located.

Service: If the potentiometer needs replaced, replace it with an identical switch.

Damper

Motor

Potentiometer,

P/N 16110

Return Air Controller (Options GE 7, 13, 14)

Function: The return air controller senses the temperature of the incoming return air.

On a two-position outside air damper system, it activates the motor to open and close

the outside air damper. On a modulating system, the return air controller maintains

100% return air until the set temperature is reached at which point the mixed air con-

troller (with or without potentiometer) controls the dampers based on the mixed air

control setting. When in the heating mode, the temperature of the “mixed” return and

outside air entering the heater must always be 35°F or above.

Service: If the controller needs replaced, replace it with an identical control.

Return Air Controller,

P/N 126170