beautypg.com

2 danger warnings and requirements, 0 maintenance and service information -6, Danger – Reznor PDH Operation Manual PreevA User Manual

Page 3

background image

Form O-PreevA, P/N 234661R8, Page 3

2.0 Maintenance

and Service

Information

This unit will operate with a minimum of maintenance. To ensure long life and satisfac-

tory performance, a heating or heating/cooling system that is operated under normal

conditions should be inspected and cleaned according to the Maintenance Schedule.

If in an area where an unusual amount of dust or soot or other impurities are present

in the air, more frequent maintenance is recommended.

When any service is completed, be careful to reassemble correctly to ensure that no

unsafe conditions are created. When re-lighting, always follow the lighting instructions

on the heater.

1.2 DANGER

Warnings and

Requirements

DANGER

Turn off the power before performing all maintenance

procedures (except to check refrigerant pressure and

temperature). Lock disconnect switch in OFF position.

When you turn off the power supply, turn off the gas (gas-

fired units). See Hazard Levels, page 2.

DANGER

If equipped with a DX cooling coil module, this unit

will contain refrigerant and may contain R410A high

pressure refrigerant.

• If equipped with a reheat pump, the reheat circuit

is charged with R410A refrigerant.

• If attached to a Reznor

®

MASA condenser unit, the

cooling circuit is charged with R410A refrigerant.

• If attached to a field-supplied condenser unit,

consult the condenser unit information to identify

the type of refrigerant.

All procedures involving any type of refrigerant should

only be performed by a qualified HVAC technician.
In addition, hazards exist with R410A that could result

in personal injury or death. Installation, maintenance,

and service should only be performed by an HVAC

technician qualified in R410A refrigerant and using

proper tools and equipment. Due to much higher

pressure of R410A refrigerant, DO NOT USE service

equipment or tools designed for R22 refrigerant.

IMPORTANT: Do not release refrigerant to the atmosphere! If

required service procedures include the adding or removing

of refrigerant, the service technician must comply with all

federal, state and local laws. The procedures discussed in

this manual should only be performed by a qualified HVAC

technician.