beautypg.com

0 maintenance procedures (cont’d) – Reznor PDH Operation Manual PreevA User Manual

Page 24

background image

Form O-PreevA, Page 24

3.7 Optional

Cooling Coil

Module (cont’d)

Reheat Module Compressor Maintenance and Replacement (cont’d)

3.7.4 Optional Reheat

Module (cont’d)

Brazing materials must be able to withstand the high pressure of R410A refriger-

ant. A high temperature, silver phosphate type brazing with 5% or greater alloy is

recommended.
To prevent oxidation, purge tubing with 2-3 psig of regulated dry nitrogen while it is

being brazed. After the unit has been properly leak tested, the nitrogen remaining in

the circuit can be used as part of the purge while brazing. Open the service valve as

needed to release the nitrogen. Do not allow moisture to enter the system.
The installer is responsible for brazing and for complying with appropriate standard

refrigerant piping procedures.

CAUTION: All brazing should be done using a 2 to 3 psig dry

nitrogen purge flowing through the pipe being brazed. See Hazard

Levels, page 2.
CAUTION: Do not open the service valves until after the condenser

unit circuits are leak tested. See Hazard Levels, page 2.
CAUTION: When brazing, protect all painted surfaces and compo-

nents from excessive heat. Wet wrap all valves but do not allow

moisture to enter the tubing. See Hazard Levels, page 2.

Step 6. Check Reheat Refrigerant Circuit for Leaks

After installation is complete, pressurize the system with helium or dry nitrogen to

approximately 150 psi (maximum pressure is 450 psi). Check for leaks using soap

bubbles or other leak-detecting methods. Repair as needed to ensure a leak free

circuit.

Step 7. Evacuate the Reheat Circuit

Use a vacuum pump and micron gauge. The circuit must be evacuated to hold a

500 micron vacuum. Vacuum must be pulled on both the discharge (high) and suc-

tions (low) side. Do the suction side first; and the compressor discharge side sec-

ond. To establish that a circuit is leak-free and moisture-free, a standing vacuum

test is recommended. Close off the valve to the vacuum pump and observe the

micron gauge. If the vacuum gauge does not rise above 500 microns in one min-

ute, the evacuation should be complete. If the vacuum gauge does rise above 500

microns in one minute, evacuation is incomplete or the system has a leak. Repeat

as needed until evacuation is complete.

NOTE Evacuation will not remove moisture from POE oil. Moisture must be pre-

vented from getting in the oil.

Continue and/or repeat

Steps 6 and 7 until evacuation is complete.

CAUTION: Do not use the replacement compressor as an

evacuation assist and never apply voltage to a compressor while

it is in a vacuum. See Hazard Levels, page 2.

Moisture and air are harmful to the system because they increase the condensing

temperature, raise the discharge gas temperature, cause formation of acids, and

cause oil breakdown.

CAUTION: Do not leave a circuit open to the atmosphere any longer

than minimum required for installation. POE oil in the compressor

is extremely susceptible to moisture absorption. Evacuation will

not remove moisture from POE oil. See Hazard Levels, page 2.

3.0 Maintenance

Procedures

(cont’d)

Step 8. Check the Electrical System

After the system has been evacuated, reconnect the electrical plug to the com-

pressor or the wires to the compressor terminals. It is a normal practice to replace

all starting components any time a compressor is changed.