beautypg.com

Reznor PDH Operation Manual PreevA User Manual

Page 32

background image

Form O-PreevA, Page 32

4.0 Troubleshooting

(cont'd)

4.2 Troubleshooting - Modulating Control Module used on

Model RDH Sizes 175-400, Model RHH, or Model SHH with

Gas Control Option AG58 or D12G (cont'd)

Gas Heat Section Modulating Control Option AG58 or D12G FUNCTIONAL ALERTS

Code

Alert

Description

Probable Causes

Solutions

Failed ignition

attempt (AO1)
Maximum

number of

allowed retries

not met

The flame could not be

established during the trial

for ignition period. This alert

indicates the maximum

number of retries has not

been exceeded and furnace

operation will continue with

another ignition attempt.

See

in the

LOCKOUT ERRORS

section, pages 33-34.

See

in the LOCKOUT ERRORS section, pages 33-34.

Lost Flame

(AO2)

The flame sensor signal

has been lost after flame is

established during a call for

heat. This alert is displayed

during the RECYCLE period

prior to the next ignition

attempt.

A. Flame sensor coated

1. Clean flame rod sensor.

B. Flame sensor improp-

erly mounted or grounded

1. Check flame sensor wiring integrity and ceramic for cracks.
2. Re-install / replace flame sensor.

C. Unstable flame pattern 1. Verify that the spacing between the burner body and the

burner shield is equal across the entire length of the burner.

2. Check that the seals between the heat exchanger header and

heat exchanger tubes are sound; refer to Paragraph 4.1.1.

3. Ensure that the heat section door gasket is in place and the

doors are properly aligned

D. Insufficient intermediate

gas manifold pressure

through main gas safety

valve

1. Check for faulty gas valve wiring.

2. Check 24 VAC to gas valve assembly.

3. Check inlet pressure to safety gas valve.

4. Check outlet pressure from the safety gas valve.

5. Replace safety gas valve if faulty.

E. Insufficient gas

manifold pressure to

burner through modulating

ball valve assembly

1. Check voltage to gas valve actuator. (2-10 VDC depending on

model)

2. Check alignment and set screw connection between ball valve

and actuator. See Paragraph 4.3.

Insufficient

Combustion

Air (AO3)
Furnace

functional

Furnace cannot achieve

desired combustion air flow

due to blockage or high

altitude operation resulting

in a de-rate of the furnace.

A. High altitude operation 1. Normal operation. Furnace automatically de-rates for high

altitude conditions.

B. Partially blocked vent

1 Check air inlet and outlet for blockage.

2. Check venting configuration for excessive venting length,

improper sizing, etc.

C. Leak in sensing hose

1. Check sensing hose for cracks, crimps, or loose connections.

D. Low Line Voltage

1. Check the line voltage to the control board. Voltage should be

within 10% of nameplate.

E. Faulty venter assembly 1. Verify that the venter assembly is functioning properly by

referring to the sensing pressure chart on page 16..

Limited Low

Fire (AO4)

Automatic adaptive program

is currently limiting the lower

range of modulation to

avoid flame loss at minimum

fire conditions. The alert is

displayed during the run

cycle once a flame-out

condition has triggered the

Limited Low Fire function.

This function is reset by

cycling power to the board.

A. Low gas line pressure 1. Ensure gas supply is connected to furnace and check for

proper line pressure.

B. Insufficient intermediate

gas manifold pressure

through gas safety valve

1. Check for faulty gas valve wiring.

2. Check 24 VAC to gas valve assembly.

3. Check inlet pressure to safety gas valve.

4. Check outlet pressure from the safety gas valve – adjust as

needed.

5. Replace safety gas valve if faulty.

C. Faulty burner operation 1. Check burner orifice for proper size and blockage.

D. Faulty flame sensor

1. Check flame rod wiring and connections.

2. Check for proper alignment of flame rod.

3. Clean flame rod sensor.

E. Improper alignment of

the modulating actuator

and the gas ball valve.

1. Check that the alignment of the actuator to the ball valve is

correct. The valve must be in the fully open position when the

actuator is energized (ACTUATOR DRIVE = 9.6 VDC or greater).

2. Ensure that the setscrew on the actuator is tightened to the

ball valve stem.

F. Blocked or improper

venting

1. Check air inlet and outlet for blockage.

2. Check venting configuration for excessive venting length,

improper sizing, etc.

Weak Flame

Signal (AO5)

The flame signal level is

less than optimal for this

furnace. Maintenance of the

flame sensing components

is advised.

A. Flame sensor coated

1. Clean flame rod sensor.

B. Flame sensor improp-

erly mounted or grounded

1. Check flame sensor wiring integrity and ceramic for cracks.

2. Re-install / replace flame sensor.

C. Unstable flame pattern 1. Verify that the spacing between the burner body and the

burner shield is equal across the entire length of the burner.

2. Check that the seals between the heat exchanger header and

heat exchanger tubes are sound; refer to Paragraph 4.1.1.

3. Ensure that the heat section door gasket is in place and the

door is properly aligned.