beautypg.com

Reznor LDAP Unit Installation Manual User Manual

Page 9

background image

Form I-LDAP, P/N 207733R6, Page 9

WARNINGS: Check the supporting structure to be used to verify that it has sufficient

load carrying capacity to support the weight of the heater. Suspend the heater only

from the threaded nut retainers or with a manufacturer provided kit. Do NOT suspend

from the heater cabinet.

See

FIGURE 1A or 1B for the appropriate hanging locations, and install the

½”-13 spring nuts in the strut that is attached to the top of the unit. Comply

with the requirements in

FIGURE 4A when using threaded rod. If ordered with

swivel connectors for 1” pipe, Option CK10, attach the swivels to the spring

nuts according to illustration in

FIGURE 4B and suspend with 1” pipe.

WARNING: All heaters must be level for proper operation. Do

not place or add additional weight to the suspended heater.

Hazard Levels, page 2.

FIGURE 4B- Swivel Connectors to

Suspend the Heater from 1” Pipe, Option

CK10

Be sure the threaded swivel connectors are

locked to the heater as illustrated.

Be sure the threaded hanger rods are locked to the

heater as illustrated. Recommended maximum hanger

rod length is 6 feet (1.8M).

Strut

attached

to top of

heater.

Lockwasher

“U”-shape

Fitting

Hex Nut

Pipe

Coupling

Assembly

Spring

Nut

Strut attached

to top of

heater.

1/2”-13

Threaded Rod

Hex Nut

Lockwasher

“U”-shape

Fitting

Spring

Nut

FIGURE 4A -

Suspending the

Heater with Rods

from the Threaded

Nut Retainers

The heater may be attached to a wall. Place supports as shown in

FIGURE 5

and comply with all guidelines listed.

5.3 Wall Mounting

Guidelines for Wall

Mounting Model

LDAP Heaters

Mounting is the responsibility of the installer. Verify that the supporting

structure has sufficient load-carrying capacity to support the weight. (See

weights, page 8.)

Prior to installation, be sure that the method of support is in agreement with

all local building codes. Check for service platform requirements.

Maintain a minimum of 2” (51mm) clearance from the discharge air

openings to structural supports. Additional clearance will be required if an

optional nozzle is to be field installed.

Determining the need for installing vibration or noise isolation is the

responsibility of the installer.

To prevent potential movement, field-supplied angles must be placed

around the perimeter of the heater to anchor it to the structural supports.

Structural supports must be placed as shown to prevent damage to the

heater.

All structural supports must be noncombustible materials.