Reznor LDAP Unit Installation Manual User Manual
Page 9
Form I-LDAP, P/N 207733R6, Page 9
WARNINGS: Check the supporting structure to be used to verify that it has sufficient
load carrying capacity to support the weight of the heater. Suspend the heater only
from the threaded nut retainers or with a manufacturer provided kit. Do NOT suspend
from the heater cabinet.
See
FIGURE 1A or 1B for the appropriate hanging locations, and install the
½”-13 spring nuts in the strut that is attached to the top of the unit. Comply
with the requirements in
FIGURE 4A when using threaded rod. If ordered with
swivel connectors for 1” pipe, Option CK10, attach the swivels to the spring
nuts according to illustration in
FIGURE 4B and suspend with 1” pipe.
WARNING: All heaters must be level for proper operation. Do
not place or add additional weight to the suspended heater.
Hazard Levels, page 2.
FIGURE 4B- Swivel Connectors to
Suspend the Heater from 1” Pipe, Option
CK10
Be sure the threaded swivel connectors are
locked to the heater as illustrated.
Be sure the threaded hanger rods are locked to the
heater as illustrated. Recommended maximum hanger
rod length is 6 feet (1.8M).
Strut
attached
to top of
heater.
Lockwasher
“U”-shape
Fitting
Hex Nut
Pipe
Coupling
Assembly
Spring
Nut
Strut attached
to top of
heater.
1/2”-13
Threaded Rod
Hex Nut
Lockwasher
“U”-shape
Fitting
Spring
Nut
FIGURE 4A -
Suspending the
Heater with Rods
from the Threaded
Nut Retainers
The heater may be attached to a wall. Place supports as shown in
FIGURE 5
and comply with all guidelines listed.
5.3 Wall Mounting
Guidelines for Wall
Mounting Model
LDAP Heaters
Mounting is the responsibility of the installer. Verify that the supporting
structure has sufficient load-carrying capacity to support the weight. (See
weights, page 8.)
Prior to installation, be sure that the method of support is in agreement with
all local building codes. Check for service platform requirements.
Maintain a minimum of 2” (51mm) clearance from the discharge air
openings to structural supports. Additional clearance will be required if an
optional nozzle is to be field installed.
Determining the need for installing vibration or noise isolation is the
responsibility of the installer.
To prevent potential movement, field-supplied angles must be placed
around the perimeter of the heater to anchor it to the structural supports.
Structural supports must be placed as shown to prevent damage to the
heater.
All structural supports must be noncombustible materials.