Reznor LDAP Unit Installation Manual User Manual
Page 15
Form I-LDAP, P/N 207733R6, Page 15
NOTE: Do not install
louvers if installing
a nozzle. Follow the
instructions shipped with
the nozzle.
Louver Installation Instructions:
1) With the wider section of the louver facing out of the heater, place
one of the compression springs over the tab on the notched end of a
louver. The end of the louver with the spring will fit in any direction in
the square opening. How the louver turns depends on which end of the
louver is inserted first.
2) Depending on the throw pattern selected, push the louver tab with the
spring into a hole in the discharge opening and insert the louver tab on
the other end into the corresponding hole on the opposite side.
3) Continue until all louvers are installed.
Adjust the louvers to provide the
desired throw pattern.
Airflow direction;
springs are on
the upper end.
Airflow direction;
springs are on
the lower end.
Wider side of the louver
blade must always be
facing out of the heater.
Compression Spring
FIGURE 8 - Use
Compression Springs
to Install Louvers
in the Discharge
Opening(s)
CAUTION: To avoid
getting burned, adjust
louvers while heater
is not operating. If
adjusting louvers
while heater is
operating, wear
gloves.
Airflow direction depends on
how the louvers are installed.
6.2.1 Installing
Louvers
After the unit is suspended/mounted, install the air directional louvers or
optional nozzle. If an optional nozzle is being installed, follow the instructions
included with the nozzle. If a nozzle is not being used, install the louvers in
the discharge opening(s). Louvers and springs are in the hardware kit shipped
with the heater.
Before actually installing the louvers, note the louver curve and determine how
the louvers should be positioned to provide the optimal throw pattern. Opening
is square so louvers may be installed either horizontal or vertical. Louvers may
be installed with the curve all the same direction (either way) or the right half
one way and left the other as illustrated in
FIGURE 8.
6.2.2 4-Way Discharge
Louvers, Option CD32
6.2.3 Discharge
Nozzle Options
Option CD57 is a 30° discharge noz-
zle.
Option CD58 is a 60° discharge
nozzle.
Option CD59 is a 30° dis-
charge nozzle with 4-way louvers. A
nozzle may be installed at each dis-
charge air opening in any direction.
NOTE: Do not install 4-way louvers
with a 60° nozzle.
Nozzles should be attached after the
unit is suspended. Follow the instal-
lation instructions in the nozzle pack-
age.
Option CD32 consists of additional louvers that are installed perpendicular to
the standard individually adjustable louvers. By installing the optional perpen-
dicular louvers, the two sets of louvers can be adjusted to direct airflow in any
of the four directions, enabling the installer to select and increase or decrease
the coverage area.
do not require the same discharge options. Each option package includes illus-
trated installation instructions.
FIGURE 9A - One heat
section with Option
CD58, 60° Nozzle
Standard individually adjustable
louvers are installed in the nozzle
discharge.