10.1.7 Fan Motor(s),

Fan Blades, and

Guard(s)

FIGURE 28 - Fan

Blade Position on

the Shaft

(76mm)

Fan

Motor

Fan

Blade

Remove dirt and grease from each motor, fan guard, and blades. Use care

when cleaning the fan blades to prevent causing misalignment or imbalance.

Check that the hub of the fan blades is secure to the shaft.

Follow these instructions for replacement of the fan guard, fan motor and/or fan

blades. Repeat the procedure for each heater section.
1. If the heater is installed, turn off the gas and disconnect the electric power.
2. Open the access door and disconnect the fan motor wires, capacitor wires

at the capacitor, and ground screw.

3. Remove the assembled parts (the fan guard, the motor and the fan blade).
4. Disassemble and replace whatever parts are needed and reassemble

using whatever part(s) are being replaced and the original parts.

Be sure the fan blade is in the proper position on the shaft; refer to the

illustration in

FIGURE 28.

10.1.8 Operating Gas

Valve(s)

Carefully remove external dirt accumulation and check the wiring connec-

tions. Size 400 has one valve; Size 800 has two valves; Size 1200 has three

valves.

WARNING: The

operating valve is

the prime safety

shutoff. All gas

supply lines must

be free of dirt

or scale before

connecting to the

heater to ensure

positive closure.

See Hazard Levels,

page 2.

The combination gas valve must be checked annually to ensure that the valve

is shutting off gas flow completely.
Instructions:
1) Locate the 1/8” NPT pressure tap on the combination valve.

Single-Stage Valve

1/8” Outlet

Pressure Tap

1/8” Outlet

Pressure Tap

Two -Stage Valve (optional

on Model LDAP 400 only)

NOTE: Operational

pressure settings and

instructions for checking

pressure settings are in

Paragraph 12.

FIGURE 29 - Pressure Tap for Checking Gas Flow Shutoff

Position the assembly on the heater. Attach

the fan guard.
Rotate the fan blade to check for adequate

clearance. If adjustment is required, loosen

the mounting screws, re-position the fan

guard, and tighten the screws. Rotate

the fan blade and re-check for adequate

clearance. Repeat this procedure until the

assembly is positioned properly.

5. Reconnect the fan motor wires according to the wiring diagram and close

the access panel.

6. When finished with all sections, restore power to the heater and turn on the

gas. Light, following the instructions on the lighting instruction plate. Check

for proper operation.