beautypg.com

Reznor LDAP Unit Installation Manual User Manual

Page 28

background image

Form I-LDAP, P/N 207733R6, Page 28

Each heat section in this

heater is equipped with

a direct spark integrated

control module (circuit

board). The module

monitors the safety

devices and controls the

operation of the fan and

venter motors and the

gas valve between heat

cycles.

8.5 Ignition System

8.4 Adjustable Air

Destratification

Fan Control

An adjustable fan control is located on top of the first heat section. It is adja-

cent to the circulating air fan and motor and controls the fan motors in all heat

sections. The purpose of the fan control is to energize the fan motor(s) when

the ambient air temperature around the heater reaches the setting on the con-

trol. The fan motor(s) will be de-energized when the fan control is satisfied.

The fan(s) re-circulates the heated air near the ceiling down to the floor level

(destratification) and improves heat recovery. A call for heat by the thermostat

overrides the air destratification fan control.
Set the adjustable fan control for the desired temperature setting for energiz-

ing the circulating air fan(s). The fan control setting should be set 5 to 10°F

higher than the wall-mounted thermostat setting. The heater is factory wired

to energize the fan(s) at medium speed when energized by the adjustable fan

control. For lower mounting heights it may be desirable to operate the fan(s) at

low speed. Switching the blue (medium speed) and red (low speed) fan motor

wires on each heat section will change the fan motor(s) speed. Refer to the

wiring diagram for the wire locations.
To manually override the fan control, the heater may be tuned off at the circuit

breaker in the main electrical panel, or a field-installed electrical box with a

SPST switch can be located near the wall thermostat with the switch wired in

series with the fan control.
The air destratification can also be a benefit in the summer time. Using the

fan(s) in the summer time can improve working conditions by alleviating stag-

nant air conditions and creating a cooling effect for the occupants.

8.3 High Limit Control

Each heat section is equipped with a temperature activated, manually reset

high limit control. The high limit control is located at the top of each heat sec-

tion. It is factory set and is non-adjustable. If the setpoint is reached, the high

limit control acts to interrupt the electric supply to the gas valve in that heat

section. If the high limit control activates, identify and correct the cause before

resetting the switch. Refer to the Maintenance Section for information on prob-

able causes . (For location, see

FIGURE 22, page 35.)

DANGER: If a manual reset high limit control activates, identify and correct the

cause before resetting the switch. Never bypass the high limit control; hazardous

conditions could result. See Hazard Intensity Levels, page 2.

FIGURE 20 –

DSI

Integrated

Control

Module

(circuit

board) in

Each Heat

Section

8.0 Controls and

Operation

(cont’d)