beautypg.com

Reznor LDAP Unit Installation Manual User Manual

Page 29

background image

Form I-LDAP, P/N 207733R6, Page 29

Normal Heat Cycle

Operating Sequence

1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal.

The control checks to see that the limit and high limit switches are closed and

the heat section pressure switch is open and the main combustion air pressure

switch (Sizes 800 and 1200) is open. If the limit or high limit switch is open,

the control responds as defined in the “Abnormal Heat Cycle, Limit Switch

Operation”. If the heat section pressure switch or main combustion air pressure

switch are closed, the control will do four flashes on the green LED and wait

indefinitely for the heat section pressure switch or main combustion air pres-

sure switch to open. If the heat section pressure switch and main combustion

air pressure switch are open, the control proceeds to prepurge.
2) Prepurge - The control energizes the heat section venter motor and main

venter motor (Sizes 800 and 1200) and waits for the heat section pressure

switch and main combustion air pressure switch to close. If the heat section

pressure switch or main combustion air pressure switch does not close within

30 seconds of the heat section venter motor and main venter motor energizing,

the control will do two flashes on the green LED. The control will leave the heat

section venter motor and main venter motor energized indefinitely as long as

the call for heat remains and the heat section pressure switch or main combus-

tion air pressure switch is open.
When the heat section pressure switch and main combustion air pressure

switch are proven closed, the control begins the prepurge time. If flame is

present any time while in prepurge, the prepurge time is restarted. If flame is

present long enough to cause lockout, the control responds as defined in “Fault

Modes, Undesired Flame”.
The control runs the heat section venter motor and main venter motor for a 20

second prepurge time, then proceeds to the ignition trial period.
3) Ignition Trial Period - The control energizes the spark and main gas valve.

The venter remains energized. If flame is sensed during the first 16 seconds,

the spark is de-energized and the control proceeds to heat fan on delay. If flame

has not been sensed during the first 16 seconds, the control de-energizes the

spark output and keeps the gas valve energized for an additional one second

flame proving period. If flame is not present after the flame proving period, the

control de-energizes the gas valve and proceeds with ignition re-tries as speci-

fied in “Abnormal Heat Cycle, Ignition Re-try”. If flame is present, the control

proceeds to the fan on delay.
4) Fan On Delay - The control waits for 30 seconds from the time the gas

valve opened and then energizes the fan motor. The gas valve, heat section

venter motor, and main venter motor remain energized. The control proceeds

to steady heat mode.
5) Steady Heat - Control inputs are continuously monitored to ensure limit, high

limit, heat section pressure switch, and main combustion air pressure switch

are closed, flame is established, and the thermostat call for heat remains.

When the thermostat call for heat is removed, the control de-energizes the gas

valve and begins post-purge and fan off delay timing.
6) Post Purge - The heat section venter motor and main venter motor outputs

remain on for a 45 second post-purge period after the thermostat is satisfied.

Interrupted Thermostat Call for Heat - If the thermostat demand for heat is

removed before the flame is recognized, the control will run the heat section

venter motor and main venter motor for the post purge period and de-energize

all outputs.
If the thermostat demand for heat is removed after successful ignition, the con-

trol will de-energize the gas valve, run the heat section venter motor and main

NOTE: All LED Flash

Codes are on page

41.

Abnormal Heat Cycle

Functions