beautypg.com

0 controls and operation, Pressure switch settings – Reznor LDAP Unit Installation Manual User Manual

Page 27

background image

Form I-LDAP, P/N 207733R6, Page 27

8.1 Combustion Air Proving [Pressure Switch(es)]

8.2 Limit Control

Each heat section is equipped with a temperature activated auto reset limit con-

trol. The control is factory set and is non-adjustable. If the setpoint is reached,

the limit control will interrupt the electric supply to the gas valve in that heat

section. This safety device provides protection in the case of motor failure or

lack of airflow due to a restriction at the inlet or outlet. (For location, see

FIG-

URE 22, page 35.)

The combustion air proving switch is a pressure sensitive switch that monitors

air pressure to ensure that proper combustion airflow is available. The switch

is a single pole/normally open device which closes when a differential pressure

is sensed between the venter housing and the flue collection box. Each section

in the heater has a pressure switch. (For switch location, see

FIGURE 22, page

35.) In addition, heaters with more than one heat section (Size 800 and Size

1200) have a main pressure switch which senses the negative pressure in the

main venter housing.
On startup when the heater is cold, the sensing pressure is at the highest level,

and as the heater and flue system warm up, the sensing pressure becomes

less. After the system has reached equilibrium (about 20 minutes), the sensing

pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pressure to

be outside the switch setpoint, the pressure switch will function to shutoff the

burner. If the main combustion air pressure switch opens, it will interrupt the

electric supply to all gas valves. If a heat section pressure switch opens, it will

interrupt the electric supply to the gas valve in that heat section. The burner(s)

will remain off until the system has cooled and/or the flue system resistance is

reduced.
The Table below lists the approximate water column differential pressure set-

tings of the heat section pressure switch(es) and the negative pressure read-

ings of the main pressure switch.

Pressure Switch

Settings

DANGER: Safe operation of this heater requires proper venting flow. NEVER bypass

combustion air proving switch(es) or attempt to operate the heater without the venter

running and the proper flow in the vent system. Hazardous conditions could result.

See Hazard Intensity Levels, page 2.

NOTE: For high

altitude, follow

instructions in

Paragraph 8.3 to

change heat section

pressure switch(es).

The main combustion

air pressure switch

(Sizes 800 and 1200

only) does not need to

be changed for a high

altitude installation.

Sea Level Pressure Switch Settings (Applies to elevations up to 6000ft/1830M)

Model LDAP

Main Pressure Switch

Heat Section Pressure Switch(es)

Start-up Cold Equilibrium

Hot

Setpoint

OFF

Setpoint

ON

Label

Color

Switch

Part No.

Qty

Start-up Cold Equilibrium

Hot

Setpoint

OFF

Setpoint

ON

Label

Color

Switch

Part No.

Negative Pressure (in. w.c.)

Differential Pressure (in. w.c.)

400

Not Applicable

1 1.80 to 1.50 1.05 to 0.85

0.65

0.83

Yellow 197028

800 -1.30 to -1.00 -0.85 to -0.65

-0.15

-0.33

Gray 205445 2 1.90 to 1.60 1.10 to 0.90

0.65

0.83

Yellow 197028

1200 -1.40 to -0.90 -0.97 to -0.59

-0.15

-0.33

Gray 205445 3 2.40 to 1.90 1.55 to 1.00

0.65

0.83

Yellow 197028

High Altitude Pressure Switch Settings, Units Above 6000ft/1830M

Model LDAP

Main Pressure Switch

Heat Section Pressure Switch(es)

Start-up Cold Equilibrium

Hot

Setpoint

OFF

Setpoint

ON

Label

Color

Switch

Part No.

Qty

Start-up Cold Equilibrium

Hot

Setpoint

OFF

Setpoint

ON

Label

Color

Switch

Part No.

Negative Pressure (in. w.c.)

Differential Pressure (in. w.c.)

400

Not Applicable

1 1.75 to 1.45 1.00 to 0.80

0.60

0.78

Lt. Blue 197029

800 -1.25 to -0.95 -0.80 to -0.60

-0.15

-0.33

Gray 205445 2 1.85 to 1.55 1.05 to 0.85

0.60

0.78

Lt. Blue 197029

1200 -1.35 to -0.85 -0.92 to -0.54

-0.15

-0.33

Gray 205445 3 2.35 to 1.85 1.50 to 0.95

0.60

0.78

Lt. Blue 197029

8.0 Controls and

Operation

CAUTION: The auto reset limit control will shut down the heater until the cause is

corrected. Do not bypass the limit control; hazardous conditions could result. See

Hazard Intensity Levels, page 2.