0 clearances and dimensions, 2 dimensions - model ldap 400, 1 clearances – Reznor LDAP Unit Installation Manual User Manual

Page 7: Figure 3a - model ldap 400, Clearances, Size

background image

Form I-LDAP, P/N 207733R6, Page 7

Instructions for

Changing Heat

section Pressure

Switch(es)
NOTE:
Do not change

the main pressure

switch located on top

of a Size 800 and Size

1200 heater. It is the

same for all elevations.

4.0 Clearances

and

Dimensions

FIGURE 3A - Model LDAP 400

NOTE: If an optional

nozzle is added to the

discharge opening, see

dimensions on page 16.

4.2 Dimensions -

Model

LDAP 400

Top

View

Bottom

View

Front

View

Right Side View

17-1/8”

(435mm)

30” (762mm)

14-7/8”

(378mm)

9-1/8”

(232mm)

15-1/4”

(384mm)

34-3/8” (873mm)

Hanger Location

1/2-13 Female Thread

28-1/8”

(714mm)

Air

Destratification

Fan Control

7/8” (22mm)

2-1/8” (54mm)

23”

584mm)

3-1/4”

(83mm)

5-5/8”

(143mm)

23”

(584mm)

Discharge Opening

43-1/2” (1105mm)

9-7/8”

(251mm)

5”

(127mm)

2-5/8”

(67mm)

13-1/8”

(333mm)

Line Voltage Connection

Disconnect Switch

1” NPT Gas Connection

38”

965mm)

1-1/4”

(32mm)

48-1/2”

(1232mm)

9-1/4” (235mm)

Thermostat

Connection

6” Flue

Outlet

4.1 Clearances

Heaters must be installed so that the clearances in the table are provided for

combustion air space, inspection and service, and for proper spacing from

combustible construction. Clearance to combustibles is defined as the mini-

mum distance from the heater to a surface or object that is necessary to ensure

that a surface temperature of 90°F above the surrounding ambient tempera-

ture is not exceeded.

Clearances

Size

Top

Flue

Connector

Front (Access

Panel)

Rear

Disconnect

Side

Side

Bottom

inches mm inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

400

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

800

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

1200

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

1. In the control compartment of the first heat section, locate the pressure

switch.

2. Mark and disconnect the two wires attached to the pressure switch.

3. Mark and disconnect the sensing tubes from the pressure switch.

4. Locate the two screws holding the switch mounting bracket. Remove the

screws (save screws) and the pressure switch.

5. Using the same screws, install the high altitude pressure switch. Attach the

sensing tubes and wires.

6. If installing a Model LDAP 400, the pressure switch change for high altitude

is complete. If installing a Model LDAP 800, repeat Steps 1-5 to change

the pressure switch on the second heat section. If installing a Model LDAP

1200, repeat Steps 1-5 to change the pressure switches on the second

and third heat sections.