Form I-LDAP, P/N 207733R6, Page 17

2) Vent Pipe Diameter

and Length

Use only one diameter of vent pipe on an installation.

Minimum vent length is 3 feet (1M).

Minimum of 1 ft (0.3M) of vertical vent required on venter outlet before

installing an elbow.

Vent pipe diameters and maximum vent lengths in the table apply to both

Hori-

zontal and Vertical vents. Add all straight sections and equivalent lengths

for elbows. The total combined length must not exceed the

Maximum Vent

Length.

Model

LDAP

Size

Venter

Outlet

Diameter

Vent Pipe

Diameter

Maximum

Vent

Length

1

Equivalent

Straight Length

for 90° Elbow

Equivalent

Straight Length

for 45° Elbow

Field-Supplied Taper Type

Connection Required at the

Venter Outlet

inches mm inches mm feet

M

feet

M

feet

M

400

6

152

6

152 45 13.7

15

4.6

7.5

2.3

None

7

178 60 18.3

8

2.4

4

1.2

6” to 7” (152 to 178mm) Increaser

800

8

203

8

203 50 15.2

15

4.6

7.5

2.3

None

10

254 45 13.7

5

1.5

2.5

0.8

8” to 10” (203 to 254mm) Increaser

1200

8

203

8

203 50 15.2

15

4.6

7.5

2.3

None

10

254 45 13.7

5

1.5

2.5

0.8

8” to 10” (203 to 254mm) Increaser

1

Includes one 90° elbow at venter outlet.

3) Venter (Flue) Outlet

Venter Outlet Attachment Requirements:

Depending on the size of vent

pipe as determined in Require-

ment 2), attach either the vent

pipe directly to the venter col-

lar or a taper-type enlarger.

4) Joints and Sealing

Provide field-supplied vent pipe as specified in Requirement No. 1.

• If using

single wall, 26-gauge or heavier galvanized pipe, secure slip-fit

connections using sheetmetal screws or rivets. Seal pipe joints either with

tape suitable for 550°F (such as Option FA1, P/N 98266) or high-tempera-

ture silicone sealant.

• If using

Category III vent pipe, follow pipe manufacturer’s instructions for

joining pipe sections. When attaching Category III pipe to the venter outlet

or the vent cap, make secure, sealed joints following a procedure that best

suits the style of Category III pipe being used.

• If installing a

double-wall (Type B) terminal pipe, follow the instructions

in

FIGURE 10C to join the double-wall pipe to a single-wall or Category III

vent pipe run. To attach the vent cap, follow instructions in

FIGURE 10B.

• If using

double-wall (Type B) vent pipe in the vent pipe run (at least 75%

of the equivalent vent length must be vertical), follow the pipe manufactur-

er’s instructions for joining pipe sections. For attaching double-wall pipe to

the heater, see

FIGURE 10A. To attach the vent cap, see FIGURE 10B.

Taper-type

Pipe Diameter

Increaser

Airflow

Follow instructions in Requirement 4). below to make

the connection for the type of pipe being used.

Model

LDAP

Size

Venter Outlet

Diameter

inches

mm

400

6

152

800

8

203

1200

8

203

FIGURE 10A -

Attaching

Double-Wall

(Type-B) Vent

Pipe to the

Venter Outlet
A double-wall

pipe run is

allowed only if

at least 75% of

the vent length is

vertical.

Figure 10A - STEP 1

To secure the connection,

spaced equal distance

around the pipe, drill and

insert three 3/4” long sheet-

metal screws through the

pipe and into the collar. Do

not over tighten the screws.

Venter

Collar

Double-

Wall

Pipe

Slide the

double-

wall pipe

over the

collar so

that the

collar is

inside the

inner pipe.

Figure 10A - STEP 2

Fill inside the pipe, around the collar, with sili-

cone sealant being sure there are no gaps.