10.1.9. Combustion

Air Pressure

Switch(es)

See

FIGURE 22, page 35, for location of the heat sec-

tion pressure switch. If it is determined that a pressure

switch needs replacing, use only the factory-authorized

replacement part that is designed for the model and size

of heater being serviced.
Size 400 has one pressure switch; Size 800 has two

heat section pressure switches and a main combustion

air pressure switch; and Size 1200 has three heat sec-

tion pressure switches and a main combustion air pres-

sure switch. The main combustion air pressure switch is

located on the top of the first heat section (see the illustra-

tion in Paragraph 10.1.6, page 38).

Main

Combustion

Air Pressure

Switch -

Models 800

and 1200

Heat

Section

Pressure

Switch

2) With the manual valve turned off to prevent flow to the gas valve, connect

a manometer to the 1/8” outlet pressure tap in the valve.

NOTE: A

manometer (fluid-filled gauge) is recommended.

3) Turn the manual valve to the ON position and the heater OFF. Use your

finger to fully block the main burner orifice for several seconds. Observe

the manometer with the orifice blocked, and if any pressure is indicated,

the gas valve is leaking.

A leaking gas valve must be replaced before

the heater is placed back in operation.

NOTE: A heater operating above 6000 ft elevation requires high altitude heat

section pressure switch(es). See Paragraph 5.

10.1.12 Transformer

See

FIGURE 22, page 35, for location. Use a voltmeter to

verify that there are 24 volts output from the transformer. If

the transformer is not functioning, it must be replaced. Use

a replacement transformer identical to the factory-installed

model.

10.1.11 High Limit

Control

A manual reset high limit control is located at the top of each

heat section. Do not reset high limit control without correct-

ing the problem. If it is determined that the limit control needs

replacing, use only a factory-authorized replacement part that

is designed for the size of heater.

10.1.14 Vent System

Check the complete vent system at least once a year. Inspection should

include all joints, seams, and the vent terminal cap. Clean openings. Replace

any defective parts.

10.1.13 Adjustable

Fan Control

See

FIGURE 22, page 35, for location. Check the wiring connec-

tions and the adjustment knob.
If it is determined that the destratification fan control needs

replacing, use only a factory-authorized replacement part that is

designed for the heater.

10.1.10 Limit Control

If it is determined that the automatic reset limit control needs

replacing, use only a factory-authorized replacement part that

is designed for the size of heater.
For approximate limit location, see

FIGURE 22, page 35.