beautypg.com

0 maintenance and service (cont’d) – Reznor LDAP Unit Installation Manual User Manual

Page 38

background image

Form I-LDAP, P/N 207733R6, Page 38

Flame Sensor

10.1.5 Heat Section

Venter Motor and

Wheel

Remove dirt and grease from the motor casing, the venter housing, and the

venter wheel. Venter motor bearings are permanently lubricated. Follow these

instructions for replacement of the venter motor and wheel assembly. Keep all

hardware removed to be used in re-assembling and installing the replacement

parts.
1. Turn off the gas and disconnect the electric power.

2. Open the burner/control compartment access panel.

3. Disconnect the three venter motor wires at the DSI control, capacitor wires

at the capacitor, and ground screw (located on the control panel).

4. Holding the venter motor, remove the six screws that attach the venter

motor mounting plate to the venter housing. Remove the motor and wheel

assembly from the heater.

5. Re-assemble with the replacement venter motor and wheel assembly. See

FIGURE 26.

6. Follow the wiring diagram to connect the venter wires.

7. Replace the access panel. Restore power to the heater and turn on the

gas. Light, following the instructions on the lighting instruction plate. Check

for proper operation.

FIGURE 26 - Venter

Wheel Position on

Shaft - applies to all

heat section venter

assemblies

7/16” (11mm) inside

Assembled Venter

Motor and Wheel

10.1.6 Main Venter Motor and Wheel (Models 800 and 1200 only)

The main venter motor and wheel is located on the top of the first heat section

of a Model LDAP 800 and 1200. The vent system attaches to the collar on the

top of the main venter housing.
Remove dirt and grease from the motor casing, the venter housing, and the

venter wheel. Venter motor bearings are permanently lubricated.
Follow the instructions in Paragraph 10.1.5 for replacement of the venter motor

and wheel assembly. Keep all hardware removed to be used in re-assembling

and installing the replacement parts. See

FIGURE 27 for venter wheel and

motor spacing.

Main

Combustion

Air Pressure

Switch

Venter

Housing

Venter

Motor

FIGURE 27- Venter

Motor and Wheel

Spacing on Main

Venter (Sizes 800 and

1200)

NOTES:

1) Do not use key provided

with the motor.

2) Locate the set screw on

the wheel approximately

180° from keyway in motor.

3) Torque set screw to

125 ±5 in/lbs.

1-1/4” (32mm)

Spacing for Flue

Collection Venter

Motor and Wheel

Assembly

Wheel

Exhauster Motor Base

Hex Nut

Flat

Washer

Screw

Motor Wire and Cable Assy

10.0 Maintenance

and Service

(cont’d)

10.1 Maintenance Procedures (cont’d)

CAUTION: Due to high voltage on the spark wire and electrode,

do not touch when energized. See Hazard Levels, page 2.

Flame Sensor - Refer to FIGURE 22 and locate the flame sensor. Disconnect

the wire; remove the screw and the flame sensor. Clean with an emery cloth.

10.1.4 Ignition System (cont’d)