beautypg.com

Reznor LDAP Unit Installation Manual User Manual

Page 13

background image

Form I-LDAP, P/N 207733R6, Page 13

CAUTION: DO NOT

bottom out the gas

valve regulator

adjusting screw.

This can result

in unregulated

manifold pressure

causing excess

overfire and heat

exchanger failure.

FIGURE 7 - Top View of Valves showing Outlet Pressure Tap

and Adjustment Locations

Single-Stage Valve

1/8” Output

Pressure Tap

Adjust Low

Pressure Output

Adjust

High

Pressure

Output

1/8” Output

Pressure Tap

Inlet

Pressure

Tap

Inlet

Pressure

Tap

Two -Stage Valve (optional on

Model LDAP 400 only)

Output

Adjustment

Screw

NOTE: If operating at

high altitude, outlet

pressure requires

adjustment. Follow

instructions below.

adjustment is necessary, remove the cap from the adjustment screw(s). Set

pressure to correct settings by turning the regulator screw IN (clockwise)

to increase pressure. Turn regulator screw OUT (counterclockwise) to

decrease pressure.

3) If installing a Model LDAP 800, repeat to verify outlet pressure on second

valve. If installing a Model LDAP 1200, repeat to verify outlet pressure

check on second and third valve.

NOTES: If installation

is above 6000 ft

(1830M), a high altitude

pressure switch is

required on each heat

section (all sizes). See

Paragraph 3.3.

The main combustion

air pressure switch

(Sizes 800 and 1200

only) does not need to

be changed for high

altitude installation.

Derate by Valve

Outlet Pressure

Adjustment for High

Altitude Operation

Manifold Pressure Settings by Altitude for the UNITED STATES

Altitude

Natural Gas (inches w.c.)

Propane Gas (inches w.c.)

Feet

Meters

Single-Stage and

Two-Stage High Fire

Two-Stage

Low Fire

Single-Stage and Two-

Stage High Fire

Two-Stage

Low Fire

0-2000

0-610

3.5

2.0

10.0

5.6

2001-3000

611-915

3.1

1.7

8.8

5.0

3001-4000

916-1220

3.0

1.7

8.5

4.8

4001-5000 1221-1525

2.8

1.6

8.1

4.6

5001-6000 1526-1830

2.7

1.5

7.7

4.4

6001-7000 1831-2135

2.6

1.5

7.4

4.2

7001-8000 2136-2440

2.5

1.4

7.1

4.0

8001-9000 2441-2745

2.4

1.3

6.7

3.8

9001-10000 2746-3045

2.4

1.3

6.7

3.6

Manifold Pressure Settings by Altitude for CANADA

Altitude

Natural Gas (inches w.c.)

Propane Gas (inches w.c.)

Feet

Meters

Single-Stage and

Two-Stage High Fire

Two-Stage

Low Fire

Single-Stage and Two-

Stage High Fire

Two-Stage

Low Fire

0-2000

0-610

3.5

2.0

10.0

5.6

2001-4500

611-1373

2.8

1.6

8.1

4.6

Instructions for High Altitude Derate

1. Determine the required valve outlet pressure for the elevation where the

heater will be operating. If unsure of the elevation, contact the local gas

supplier.

Valve Outlet Pressure Settings by Elevation

2. Locate the 1/8” output pressure tap on the first valve (See FIGURE 7). Turn

the knob on the top of the valve to “OFF”. Connect a manometer to the 1/8”

pipe outlet pressure tap in the valve. Use a water column manometer that

is readable to the nearest tenth of an inch.

3. Single-Stage and Two-Stage High Fire - Turn the knob on the top of the

valve to “ON”. Remove the cap from the pressure adjusting screw and

adjust the gas train pressure to the pressure selected from the table above.