beautypg.com

Reznor LDAP Unit Installation Manual User Manual

Page 20

background image

Form I-LDAP, P/N 207733R6, Page 20

Check the rating plate on the heater for the supply voltage and current require-

ments. A dedicated line voltage supply with disconnect switch should be run

directly from the main electrical panel to the heater. All external wiring must be

within approved conduit and have a minimum temperature rise rating of 60°C.

Conduit must be run so as not to interfere with the heater access panel.

7.1 Supply Wiring

All electrical wiring and connections, including electrical grounding MUST be

made in accordance with the National Electric Code ANSI/NFPA No. 70 (lat-

est edition) or, in Canada, with CSA Standard C22.1. In addition, the installer

should be aware of any local ordinances or gas company requirements that

might apply.

7.0 Electrical and

Wiring

Use either an optional thermostat available with the heater or a field-supplied

24-volt thermostat. Install according to the thermostat manufacturer’s instruc-

tions, paying particular attention to the requirements regarding the location of

the thermostat.

Disconnect Switch
FIGURE 13 - Built-in

Disconnect Switch

CAUTION: Route wires so that they do not contact the flue

wrapper or venter housing. When running electrical conduit,

be careful that it is clear of all access panels.

The heater is equipped with a built-in, non-fusible, lockable disconnect switch

(

FIGURE 8). If a fusible disconnect is required, it must be field supplied. The

built-in disconnect switch requires copper wiring with ampacity based on 60°C

maximum temperature rating at the line side terminals.

WARNING: To prevent injury or death due to electrocution or

contact with moving parts, lock disconnect switch open. See

Hazard Levels, page 2.

WARNING: If you turn off the power supply, turn off the gas.

See Hazard Levels, page 2.

Model LDAP supply wiring enters above and connects directly to the discon-

nect switch (See

FIGURE 3A or 3B in Paragraph 4 and FIGURE 13). A circuit

board (See

FIGURE 19 in Paragraph 8.5) is located in the control compartment

of each heat section. The circuit boards are polarity sensitive. It is advisable to

check the electrical supply to be certain that the black wire is the “hot” wire and

that the white wire is the neutral wire. The supply connection made to “L1” on

the disconnect switch

must be the “hot” wire.

Each heat section in the heater has a terminal strip for 24-volt thermostat con-

nections. The terminal strip is located on the outside of the cabinet at the front

of each heat section (See

FIGURE 3A or 3B in Paragraph 4). Wires from the

terminal strip(s) are factory wired to the circuit board(s).

7.2 24V Control

Wiring

Thermostat and

Connections

Make thermostat connections at the terminal strip on the front of the heater.

The strip has seven terminals, R, G, C, Y1, Y2, W1, and W2. Refer to the wiring

diagram on the heater.

IMPORTANT: All heaters MUST be operated by a 24-volt thermostat. Never

use a line voltage disconnect switch as a means of operating the heater. Oper-

ating by means other than a 24-volt thermostat may result in the high limit con-

trol tripping and may cause damage to the heater from excessive heat.
Connections for Reznor optional thermostats are shown by option and Size in

FIGURES 14, 15, and 16.