beautypg.com

Appendix b: unit specifi cations, Gf-125 – AERCO Esteem O&M Manual User Manual

Page 94

background image

88

Figure 31: Esteem 399 Low NOx Electronic Components

Item

Part #

Description

1

64061

Esteem 399 Low NOx Control Module

2

64062

Transformer with Surge Protection

3

64063

Esteem 399 Low NOx Control Module Display

Appendix B: Unit Specifi cations

1.

Input and output ratings are shown for sea level applications. The Esteem 399 Low NOx

automatically derates the input at approximately 2% for every 1,000 Ft. of altitude. No alterations
to the boiler or burner system is required.
2.

The IBR rating is based on a piping and pick up allowance of 1.15. This allowance should

be sufficient for the standard radiation requirements for a building load.

Fuel

Natural Gas

Input

1

399,000

Output

1

379,000

Net IBR Rating

2

330,000

Combustion Efficiency

94.1%

Thermal Efficiency

95.1%

Shipping Weight

225 lbs./ 102 Kg

Esteem 399 Low NOx output rating is based on the thermal efficiency.