Warning, Check ventilation air openings, Inspect vent and combustion air piping – AERCO Esteem O&M Manual User Manual

Page 70: Check boiler system, Gf-125

background image

64

Clean Condensate Drain Assembly

Clean Condensate Drain Assembly

1. Loosen the retaining nut from the conden-

sate drain assembly and disconnect the
assembly from the boiler.

2. Empty any water from the trap and drain

assembly. Flush with fresh water as nec-
essary to clean.

3. Check the drain piping from the conden-

sate drain assembly to the drain. Flush to
clean as necessary.

4. Reassemble the condensate drain

assembly onto the boiler by tightening
the retaining nut with rubber seal onto the
boiler. Hand tight only.

5. Remove the fill plug on the condensate

drain assembly and fill with water. See
Figure 16 on page 28.

6. Replace the fill plug on drain assembly.

Check Ventilation Air Openings

Verify that all ventilation openings to the
mechanical room or building are open and
unobstructed. Check the operation and wiring
of any automatic ventilation dampers.

Check and verify the vent discharge and the
combustion air intake are free of debris and
obstructions.

Inspect Vent and Combustion Air
Piping

Visually inspect the venting system and com-
bustion air piping for blockage, deterioration or
leakage. Repair any deficiencies.

Verify that the combustion air inlet piping is
connected, sealed and properly supported.

WARNING!

F

AILURE

TO

INSPECT

THE

VENT

SYSTEM

AND

COMBUSTION

AIR

INLET

PIPING

AND

TO

HAVE

ANY

CONDITIONS

REPAIRED

,

CAN

RESULT

IN

SE

-

VERE

PERSONAL

INJURY

OR

DEATH

.

Check Boiler System

Verify all system components are correctly
installed and operating properly.

Check the cold fill pressure for the system,
typical cold water fill pressure is 12 psig.

Verify the system pressure, as the unit operates
at high temperature, to ensure the pressure
does not exceed 25 psig. Excessive pressure
reading indicates expansion tank sizing is incor-
rect or system performance problems.

Inspect air vent and air separators in the
system. Remove the caps on automatic air
vents and briefly depress the valve stem to
flush vent. Replace the cap when completed.
Ensure vents do not leak, replace any leaking
vents.