E 02, E 03, E 04 – AERCO Esteem O&M Manual User Manual
Page 85: E 05, E 06, E 07, E 08

79
GF-125
E 02
Continued
Failed Ignition Error
Boiler has failed to
establish flame detec-
tion during the igni-
tion sequence.
•
Flame is established during the ignition sequence, but not maintained. May be due to low
flame signal detection by Control module.
•
Inspect flame pattern on the burner head during high and low fire inputs (See page 49).
Inspect and clean the burner head. Replace the burner head if damaged.
•
Check the input rate of the boiler at the gas meter during high fire input. If the gas meter
measured rate is not at or below 15% of the boiler rating, replace the gas valve.
•
Note: Length of venting and combustion air piping will affect the measure boiler rating.
•
Check the ground lead for a secure connection from Control module ground to the burn-
er mounting plate. Use a ground continuity check to verify a good ground.
•
Remove the ignition electrode. Inspect for damage. Clean white oxides off the electrode.
Replace the electrode if damaged or will not clean.
E 03
Gas Valve Harness
•
Ensure gas valve rectifier cable is properly connected to the gas valve and secured.
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, replace the rectifier cable.
E 04
Loss of Power
Power to the boiler
is lost after a lockout
has occurred.
The boiler must be manually reset and the original lockout code will be lost.
•
Will also occur if the service technician tries to reset a hard lockout by turning the boiler
OFF and then ON as an attempt to reset the boiler.
•
Verify polarity and proper ground on incoming 120V power connections
•
May occur in rare cases if there is power interruption, surge or “Dirty” voltage. A relay kit is
available and may be installed on the incoming voltage to the boiler.
E 05
Internal Failure
Short in either the
ignition cable or dis-
play panel.
•
Check flat ribbon cable to display for short.
•
Check for moisture at display and repair cause of moisture, dry and/or replace display.
•
Inspect ignition cable replace if necessary.
•
Reset the boiler control module and retry ignition sequence and boiler operation.
•
If problem continues, contact AERCO International Technical Support for additional assis-
tance.
E 06
Internal Failure
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 07
Internal Failure
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 08
Internal Failure
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.