GF-125

E 02

Continued

Failed Ignition Error

Boiler has failed to

establish flame detec-

tion during the igni-

tion sequence.

Flame is established during the ignition sequence, but not maintained. May be due to low

flame signal detection by Control module.

Inspect flame pattern on the burner head during high and low fire inputs (See page 49).

Inspect and clean the burner head. Replace the burner head if damaged.

Check the input rate of the boiler at the gas meter during high fire input. If the gas meter

measured rate is not at or below 15% of the boiler rating, replace the gas valve.

Note: Length of venting and combustion air piping will affect the measure boiler rating.

Check the ground lead for a secure connection from Control module ground to the burn-

er mounting plate. Use a ground continuity check to verify a good ground.

Remove the ignition electrode. Inspect for damage. Clean white oxides off the electrode.

Replace the electrode if damaged or will not clean.

E 03

Gas Valve Harness

Ensure gas valve rectifier cable is properly connected to the gas valve and secured.

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, replace the rectifier cable.

E 04

Loss of Power

Power to the boiler

is lost after a lockout

has occurred.

The boiler must be manually reset and the original lockout code will be lost.

Will also occur if the service technician tries to reset a hard lockout by turning the boiler

OFF and then ON as an attempt to reset the boiler.

Verify polarity and proper ground on incoming 120V power connections

May occur in rare cases if there is power interruption, surge or “Dirty” voltage. A relay kit is

available and may be installed on the incoming voltage to the boiler.

E 05

Internal Failure

Short in either the

ignition cable or dis-

play panel.

Check flat ribbon cable to display for short.

Check for moisture at display and repair cause of moisture, dry and/or replace display.

Inspect ignition cable replace if necessary.

Reset the boiler control module and retry ignition sequence and boiler operation.

If problem continues, contact AERCO International Technical Support for additional assis-

tance.

E 06

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 07

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 08

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.