beautypg.com

Chapter 17 maintenance schedule, Warning, 62 professional maintenance – AERCO Esteem O&M Manual User Manual

Page 68: Owner maintenance, Gf-125

background image

62

Professional Maintenance

At least on an annual basis the following main-
tenance should be performed by a qualified
service technician:

General
• Attend to any reported problems.
• Inspect the interior of the boiler jacket area;

clean and vacuum if necessary.

• Clean the condensate drain assembly and

fi ll with fresh water.

• Check for leaks: water, gas, fl ue and con-

densate.

• Verify

fl ue vent piping and air inlet piping

are in good condition, sealed tight and
properly supported.

• Check boiler water pressure, piping and

expansion tank.

• Check control settings.
• Check ignition electrode (sand off any

white oxide; clean and reposition).

• Check ignition wiring and ground wiring.
• Check all control wiring and connections.
• Check

burner

fl ame pattern (stable and

uniform).

Additional items if combustion or performance
is poor:
• Clean heat exchanger and fl ue ways.
• Remove burner assembly and clean burn-

er head using compressed air only.

Once the maintenance items are completed,
review the service with the owner.

Owner Maintenance

• On going as conditions warrant:
• Check the area around the unit.
• Check and remove any blockage from the

combustion air inlet and ventilation open-
ings.

• Check the temperature and pressure

gauges.

• Monthly:
• Check vent piping.
• Check combustion air inlet piping.
• Check the pressure relief valve.
• Check the condensate drain system.

• Every 6 months:
• Check boiler piping and gas supply piping

for corrosion or potential signs of leakage.

• Operate the pressure relief valve.

WARNING!

F

AILURE

TO

PERFORM

THE

SERVICE

AND

MAIN

-

TENANCE

OR

FOLLOW

THE

DIRECTIONS

IN

THIS

MANUAL

COULD

RESULT

IN

DAMAGE

TO

THE

E

STEEM

399 L

OW

NO

X

OR

SYSTEM

COMPO

-

NENTS

,

RESULTING

IN

SEVERE

PERSONAL

IN

-

JURY

,

DEATH

OR

SUBSTANTIAL

PROPERTY

DAM

-

AGE

.

Chapter 17

Maintenance Schedule

GF-125