Chapter 4 unit preparations, Warning, 14 handling instructions – AERCO Esteem O&M Manual User Manual
Page 20: Wall mounting installation, Wall mounting guidelines, Stud wall installation, Gf-125

14
Handling Instructions
The Esteem 399 Low NOx is generally easier
to handle and maneuver once removed from
the shipping carton.
To remove the shipping carton:
C
AUTION
Use care not to lift the unit from, or
place the unit on the front plastic con-
trol panel, damage can occur. Use care
not to drop, bump or rotate the boiler
upside down, as damage to the boiler
will result.
1. Remove any shipping straps and open
the side of the shipping carton.
2. Slide the unit with the foam inserts out of
the carton.
3. Discard all packing materials.
Wall Mounting Installation
The Esteem 399 Low NOx should be wall
mounted using the bracket provided with
the boiler. The Esteem 399 Low NOx is not
designed for floor installation. If floor installa-
tion is required an optional floor stand is avail-
able through AERCO International.
WARNING
T
HE
WALL
USED
FOR
MOUNTING
THE
E
STEEM
399 L
OW
NO
X
MUST
BE
VERTICALLY
PLUMBED
AND
CAPABLE
OF
SUPPORTING
A
MINIMUM
250
POUNDS
[115 K
G
]
FOR
E
STEEM
399 L
OW
NO
X
. F
AILURE
TO
COMPLY
WITH
THESE
REQUIRE
-
MENTS
COULD
RESULT
IN
PERSONAL
INJURY
,
DEATH
OR
SUBSTANTIAL
PROPERTY
DAMAGE
.
Wall Mounting Guidelines
• The boiler is heavy and bulky. A minimum
of 2 people is required for mounting the
boiler.
• DO NOT mount or attempt to mount the
wall bracket to hollow sheet rock or lath
walls using anchors. Only install boiler to
studs or equivalent wood structure.
• The wall-mounting bracket is designed
for stud spacing of 12 inch or 16 inch on
centers. For unconventional stud spacing,
a solid / secure mounting surface must be
provided for installation of the bracket.
• For mounting on wood studs, install the
bracket using the lag screws provided with
the boiler. Ensure both lag screws are
installed securely in the studs.
• For mounting on metal studs, install the
bracket to the studs using 3/16” toggle
bolts and washers.
• For mounting on solid walls (rock, concrete,
brick, cinder block, etc.), install the wall
bracket using anchors (double expansion
shields) and bolts with washers provided
with the boiler.
WARNING
U
SE
EXTREME
CARE
NOT
TO
DROP
THE
BOILER
OR
CAUSE
BODILY
INJURY
WHILE
LIFTING
OR
MOUNTING
THE
BOILER
ONTO
THE
BRACKET
.
O
NCE
MOUNTED
VERIFY
THAT
THE
BOILER
IS
SECURELY
ATTACHED
TO
THE
BRACKET
AND
WALL
. F
AILURE
TO
COMPLY
WITH
THE
ABOVE
GUIDELINES
COULD
RESULT
IN
PROPERTY
DAM
-
AGE
,
PERSONAL
INJURY
OR
DEATH
.
Stud Wall Installation
• To distribute the weight of the boiler evenly
when mounting onto a stud wall it is rec-
ommended to use the Esteem 399 Low
NOx Wall Frame kit.
• When using the wall frame to mount the
boiler reference the kit installation instruc-
tions and ensure the frame is securely
fastened to the wall.
• If the structure of wall is questionable,
in supporting a minimum weight of 250
pounds [115 kg.], it is recommended to use
the optional fl oor stand.
Wall Bracket Installation - Solid Walls
Chapter 4
Unit Preparations
GF-125