background image

84

GF-125

E 52

Flue Temperature

Sensor

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 60

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 61

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 65

Blower Assembly

Control module does not detect proper blower operation during a call for heat.

Disconnect the 35V dc connector at the blower. Restart the boiler sequence and check for

35Vdc at the connector between the black and white wires (pin 1 & 5).

If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure

a secure connection. Replace the blower assembly if problem is not resolved.

If 35Vdc is not present at the connector, inspect the wiring harness for any visible signs

of damage. If the wire harness inspection does not resolve the problem, contact AERCO

International Technical Support for additional assistance.

Telephone Support

(800) 526-0288

Direct to AERCO Technical Support

(8 to 5 pm EST

, Monday through Friday)

Please have the unit’

s model number and the serial number from the rating label on the backside of the control panel when calli

ng

about service or troubleshooting.

Model #_________________________

Serial #__________________________