B 38, B 40, B 52 – AERCO Esteem O&M Manual User Manual
Page 83: B 65, B 116, B 118

77
GF-125
b 38
Indirect Water Heater
Temperature Sensor
Control module detects
“open” indirect water
heater temperature sen-
sor.
Typically an improper or missing connection of the sensor.
•
Review parameter setting for DHW operating signal selection. See Esteem Control
Supplement GF-125C for proper selection.
•
Inspect the DHW temperature sensor and wiring, ensure it is secure and in good condition.
•
Replace the sensor if problem persists.
b 40
Flue Temperature Sensor
Control module detects
“open” flue temperature
sensor.
Typically an improper or missing connection at the sensor.
•
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition.
•
Replace the sensor if problem persists.
b 52
Flue Temperature Sensor
Control module detects
flue temperature greater
than 241ºF, less than
250ºF. Burner off for 150
seconds
•
An indication the heat exchanger flue ways may need cleaning.
See page 68 for procedures
on cleaning.
•
Isolate the boiler from the boiler system piping and drain the boiler heat exchanger.
Flush
the boiler heat exchanger several times, checking the discharge water for signs of scale or
sediment.
•
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition,
replace as needed.
•
Replace the sensor if problem persists.
b 65
Blower Assembly
Control module does
not detect proper blower
operation during a call for
heat.
•
Disconnect the 35Vdc connector at the blower. Restart the boiler sequence and check for
35Vdc at the connector between the black and white wires (pin 1 & 5).
•
If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure
a secure connection. Replace the blower assembly if problem is not resolved.
•
If 135Vdc is not present at the connector, inspect the wiring harness. Replace the wire
harness if the inspection reveals any signs of damage.
•
Contact AERCO International Technical Support if problem is not resolved
b 116
Incoming Voltage
Frequency
Inadequate power to con-
trol module
Control module requires an incoming voltage of 120V and a frequency of 60 Hz.
•
If the incoming voltage is being supplied by a generator or alternative source, check the
frequency supplied and adjust accordingly.
b 118
Flame Current Signal
Lost
- Contact AERCO International Technical Support for further assistance.