B 38, B 40, B 52 – AERCO Esteem O&M Manual User Manual

Page 83: B 65, B 116, B 118

background image

77

GF-125

b 38

Indirect Water Heater

Temperature Sensor

Control module detects

“open” indirect water

heater temperature sen-

sor.

Typically an improper or missing connection of the sensor.

Review parameter setting for DHW operating signal selection. See Esteem Control

Supplement GF-125C for proper selection.

Inspect the DHW temperature sensor and wiring, ensure it is secure and in good condition.

Replace the sensor if problem persists.

b 40

Flue Temperature Sensor

Control module detects

“open” flue temperature

sensor.

Typically an improper or missing connection at the sensor.

Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition.

Replace the sensor if problem persists.

b 52

Flue Temperature Sensor

Control module detects

flue temperature greater

than 241ºF, less than

250ºF. Burner off for 150

seconds

An indication the heat exchanger flue ways may need cleaning.

See page 68 for procedures

on cleaning.

Isolate the boiler from the boiler system piping and drain the boiler heat exchanger.

Flush

the boiler heat exchanger several times, checking the discharge water for signs of scale or

sediment.

Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition,

replace as needed.

Replace the sensor if problem persists.

b 65

Blower Assembly

Control module does

not detect proper blower

operation during a call for

heat.

Disconnect the 35Vdc connector at the blower. Restart the boiler sequence and check for

35Vdc at the connector between the black and white wires (pin 1 & 5).

If 35Vdc is present at the connector, reconnect the wire harness to the blower and ensure

a secure connection. Replace the blower assembly if problem is not resolved.

If 135Vdc is not present at the connector, inspect the wiring harness. Replace the wire

harness if the inspection reveals any signs of damage.

Contact AERCO International Technical Support if problem is not resolved

b 116

Incoming Voltage

Frequency

Inadequate power to con-

trol module

Control module requires an incoming voltage of 120V and a frequency of 60 Hz.

If the incoming voltage is being supplied by a generator or alternative source, check the

frequency supplied and adjust accordingly.

b 118

Flame Current Signal

Lost

- Contact AERCO International Technical Support for further assistance.