E 31, E 32, E 35 – AERCO Esteem O&M Manual User Manual
Page 89: E 36, E 37, E 40, E 44

83
GF-125
E 31
Boiler Supply
Temperature Sensor
Control module detects a short or jumped out condition of the boiler supply (outlet) temperature
sensor.
•
Inspect the boiler supply temperature sensor and wiring, ensure it is secure and in good
condition, replace as needed.
•
Replace the sensor and wiring if problem persists.
E 32
Boiler Return
Temperature Sensor
Control module detects a short or jumped out condition of the boiler return (inlet) temperature
sensor.
•
Inspect the boiler return temperature sensor and wiring, ensure it is secure and in good con-
dition, replace as needed.
•
Replace the sensor and wiring if problem persists.
Control module detects a short or jumped out condition of flue temperature sensor.
•
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition.
•
Replace the sensor and wiring if problem persists.
E 35
Flue Temperature
Sensor
Control module detects the boiler supply (outlet) temperature sensor as an open circuit.
•
Inspect the boiler supply temperature sensor and wiring, ensure it is secure and in good
condition, replace as needed.
E 36
Boiler Supply
Temperature Sensor
Control module detects the boiler return (inlet) temperature sensor as an open circuit.
•
Inspect the boiler return temperature sensor and wiring, ensure it is secure and in good con-
dition, replace as needed.
E 37
Boiler Return
Temperature sensor
Control module detects the flue temperature sensor as “open”, which is typically an improper or
missing connexion at the sensor.
•
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition.
•
Replace the sensor if problem persists.
E 40
Flue Temperature
Sensor
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 44
Internal Failure
Control module
detects the flue tem-
perature exceeding
the 250
ºF limitation of
the boiler.
•
Heat exchanger flue ways may need cleaning. See Chapter 18
Maintenance Procedures for
cleaning the flue side of the heat exchanger.
•
Isolate the boiler from the boiler system piping and drain the boiler heat exchanger. Flush
the boiler heat exchanger several times, checking the discharge water for signs of scale
or sediment.
•
Inspect the flue temperature sensor and wiring, ensure it is secure and in good condition,
replace as needed.