E 15, E 16, E 17 – AERCO Esteem O&M Manual User Manual
Page 87: E 18, E 19, E 24

81
GF-125
E 15
Internal Failure
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 16
Internal Failure
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 17
Internal Failure
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.
E 18
High Temperature
Limit, Supply
Temperature
Boiler supply water
temperature exceeds
212
ºF.
•
Check the following.
•
The boiler and heating system are filled with water and the LWCO is operating properly.
•
The boiler and heating system have been properly purged and there is no trapped air.
•
Inspect heating system piping and its components. Ensure piping is per the recommenda-
tions given in this Installation Manual or other approved design configurations.
•
Use a device to measure the supply water temperature leaving the boiler. Compare this
measured temperature with the display temperature (See page 52.)
•
Replace supply temperature sensor if temperature comparison is off by more than 10
ºF.
E 19
High Temperature
Limit, Return
Temperature
Boiler return water
temperature exceeds
212
ºF.
Check the following:
•
The boiler and heating system are filled with water and the LWCO is operating properly.
•
The boiler and heating system have been properly purged and there is no trapped air.
•
Inspect heating system piping and its components. Ensure piping is per the recommenda-
tions given in this manual or other approved design configurations.
•
Ensure boiler piping is correct and water flow is not reversed nor pipes cross-connected.
•
Use a device to measure the return water temperature leaving the boiler. Compare this
measured temperature with the display temperature (See page 52.)
•
Replace return temperature sensor if temperature comparison is off by more than 10
ºF
.
E 24
Low Voltage Internal
Short or Voltage
Feedback
Short or voltage
feedback in the 24V
circuit.
Check the following:
•
Line voltage to the boiler for polarity and 120VAC. Ensure the boiler is on a dedicated line. If
voltage is supplied from “OFF-GRID” source, check conditions.
•
Moisture on and around the low voltage terminal strip on the boiler. Resolve moisture issue.
•
Moisture on the display. Resolve moisture issue and replace the display panel.
•
Voltage feedback to Terminals 7 and 8, Terminals 11 and 12, and Terminals 17 and 18.
•
Remove all field wiring from the boiler and reset the boiler control module.
•
Initiate a call for heat external to the boiler and check for voltage on field wiring to termi-
nals 7 and 8 (space heating) and terminals 11 and 12 (DHW heating).
•
Reset the boiler control module and retry ignition sequence and boiler operation. If problem
continues, contact AERCO International Technical Support for additional assistance.