81

GF-125

E 15

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 16

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 17

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 18

High Temperature

Limit, Supply

Temperature

Boiler supply water

temperature exceeds

212

ºF.

Check the following.

The boiler and heating system are filled with water and the LWCO is operating properly.

The boiler and heating system have been properly purged and there is no trapped air.

Inspect heating system piping and its components. Ensure piping is per the recommenda-

tions given in this Installation Manual or other approved design configurations.

Use a device to measure the supply water temperature leaving the boiler. Compare this

measured temperature with the display temperature (See page 52.)

Replace supply temperature sensor if temperature comparison is off by more than 10

ºF.

E 19

High Temperature

Limit, Return

Temperature

Boiler return water

temperature exceeds

212

ºF.

Check the following:

The boiler and heating system are filled with water and the LWCO is operating properly.

The boiler and heating system have been properly purged and there is no trapped air.

Inspect heating system piping and its components. Ensure piping is per the recommenda-

tions given in this manual or other approved design configurations.

Ensure boiler piping is correct and water flow is not reversed nor pipes cross-connected.

Use a device to measure the return water temperature leaving the boiler. Compare this

measured temperature with the display temperature (See page 52.)

Replace return temperature sensor if temperature comparison is off by more than 10

ºF

.

E 24

Low Voltage Internal

Short or Voltage

Feedback

Short or voltage

feedback in the 24V

circuit.

Check the following:

Line voltage to the boiler for polarity and 120VAC. Ensure the boiler is on a dedicated line. If

voltage is supplied from “OFF-GRID” source, check conditions.

Moisture on and around the low voltage terminal strip on the boiler. Resolve moisture issue.

Moisture on the display. Resolve moisture issue and replace the display panel.

Voltage feedback to Terminals 7 and 8, Terminals 11 and 12, and Terminals 17 and 18.

Remove all field wiring from the boiler and reset the boiler control module.

Initiate a call for heat external to the boiler and check for voltage on field wiring to termi-

nals 7 and 8 (space heating) and terminals 11 and 12 (DHW heating).

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.