5-1 Troubleshooting
5-3
5
Appe
ndi
x
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -
Communication error indicator (L ERR)
This lamp lights when the DL-CL1 is not communicating properly with the CC-Link
maser station.
Condition
Condition
Corrective action
Not lit
Communicating correctly.
–
Lighting in red
• The data link is not con-
figured properly.
• The DL-CL1 is config-
ured for Ver. 2 (monitor 
mode 2/full mode) while 
the master station is con-
figured for Ver. 1.
Check that the data link is properly 
configured, and then turn off the 
power to the DL-CL1 and back on.
Flashing in red
(At regular 
intervals)
The setting of the transmis-
sion rate setting switch, 
operating mode setting 
switch, or station number 
setting was changed while 
in operation.
If you changed the setting intention-
ally, turn off the power and back on. 
The new setting is applied.
If you changed the setting uninten-
tionally, restore the previous setting. 
Normal condition is automatically 
recovered.
Flashing in red
(At irregular 
intervals)
The termination resistor is 
not connected correctly.
Connect the termination resistor cor-
rectly. (Normal condition is automati-
cally corrected after the cause is 
removed.)
Affected by noise.
Implement noise protection on the 
DL-CL1 and CC-Link cable. (Normal 
condition is automatically corrected 
after the cause is removed.)