1 specifications, Specifications -2, Specifications – KEYENCE DL-CL1 User Manual
Page 66

4-2
4
Sp
eci
fic
at
io
ns
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -
4-1
Specifications
*1
"D-bus" is the name of KEYENCE's wiring-saving system for sensor amplifiers.
*2
Depends on the type of sensor amplifiers connected (Up to 8 sensor units can
be connected to the SK-1000 series.).
Product name
CC-Link compatible communication unit
Model
DL-CL1
Communication method
CC-Link compliant
CC-Link specifi-
cations
Compatible ver-
sions
Ver. 2.00/Ver. 1.10 (selectable)
Number of occu-
pied stations
Ver. 2.00: 1 station, 8x / 2 stations, 8x / 4 stations, 2x; (selectable)
Ver. 1.10: 1 / 2 / 3 / 4 stations (selectable)
Type of station
Remote device station
Transmission
rate
156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps
Setting of sta-
tion numbers
1 to 64
Sensor amplifier
connection
specifications
Connectable
sensors
Sensor amplifiers with D-bus support
*1
Number of con-
nectable sensor
units
15 units max.
*2
Indicators
Power indicator: Green LED
Communication indicator (L_RUN): Green LED
Communication error indicator (L_ERR): Red LED
Sensor communication indicator: 2-color (green/red) LED
Power voltage
20 to 30 VDC, including ripple (P-P) 10%
(supplied from the connected sensor amplifiers)
Power consumption
1560 mW or less (at 24 V, 60 mA max.)
Environmental
resistance
Operating ambi-
ent temperature
0 to +55
°C (no freezing)
Operating ambi-
ent humidity
35 to 85% RH (no condensation)
Vibration resis-
tance
10 to 55 Hz, compound amplitude 1.5 mm, 2 hours each in X, Y, Z directions
Pollution degree 2
Materials
Main unit case and dust cover: Polycarbonate
CC-Link connector: Polyamide (plug), PBT (socket)
Weight (including connectors)
Approx. 80 g