Installing a solid state drive on the server board – Kontron NSN2U IP Network Server User Manual
Page 54

53
Figure 45. Installing the Z-U130 Drive on the FP Board
Installing a Solid State Drive on the Server Board
1. Remove the back chassis cover. For instructions, see “Removing the Back Cover” in
2. Remove the riser card assembly. For instructions, see “Removing the Riser Card
3. Remove the processor air duct. For instructions, see “Removing the Processor Air
Locate the white plastic standoff on the server board. (
4. Figure 46 “A”)
5. Insert the drive module onto the server board by connecting drive module to the
standoff on the server board and the connector on the module onto the server board
header. (“B”)
6. If this is the last task you are performing, re-install the processor air duct, the
riser card assembly, and the back chassis cover. For instructions, see Section 3.2.
Reconnect all external devices and the power cord(s).
Figure 46. Installing the Z-U130 Drive on the Server Board