LDAT-Series Integrated Linear Thrusters 47

Rockwell Automation Publication LDAT-IN001A-EN-P - August 2012

Home

Follow these steps to home the linear thruster.

1.

From the Workspace, select Mode Configuration>Homing.

2.

Set the parameters to the following values.

If linear thruster does not move to negative spring stop during homing it may be
necessary to increase the Home Current Value.

3.

From the Workspace, select Indexing.

4.

Set the parameter Auto Start Index to Off.

5.

Click Indexing Control Panel.

6.

Click Enable Drive.

7.

Click Start Homing.

The linear thruster moves to the negative spring stop and returns to the home position.

The In Position and At Home display indicators turn yellow.

Parameter

Value

Home Type

Home to Current Value/Back to Marker

Auto Start Homing on Enable

Inactive

Home Sensor Back-off

Inactive

Homing Velocity

-0.0100 m/s

Homing Accel/Decel

1.0000 m/s/s

Offset Move Distance

2000.0000 counts

Stop Home Decel

1.0000 m/s/s

Home Sensor Polarity

Active Going Transition

Home Position

0.000 counts

Creep Velocity

0.0100 m/s

Home Current Value

2.0000 Amps