Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual
Page 30

Publication 1797-6.5.1 - May 2005
2-14 Understanding Configurable FLEX Ex Analog Module Features
Analog Input Modules (1797-IE8 and -IE8NF) Image Table
Mapping
Table 2.6 Input Map (Read Words)
Table 2.7 Output Map (Write Words)
Bit
→
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
↓
Read
0
Channel 0 Input Data
1
Channel 1 Input Data
2
Channel 2 Input Data
3
Channel 3 Input Data
4
Channel 4 Input Data
5
Channel 5 Input Data
6
Channel 6 Input Data
7
Channel 7 Input Data
8
Ovr
Alm
ch
7
Ovr
Alm
ch
6
Ovr
Alm
ch
5
Ovr
Alm
ch
4
Ovr
Alm
ch
3
Ovr
Alm
ch
2
Ovr
Alm
ch
1
Ovr
Alm
ch
0
Und
Alm
ch
7
Und
Alm
ch
6
Und
Alm
ch
5
Und
Alm
ch
4
Und
Alm
ch
3
Und
Alm
ch
2
Und
Alm
ch
1
Und
Alm
ch
0
9
Rm
Flt
ch
7
Rm
Flt
ch
6
Rm
Flt
ch
5
Rm
Flt
ch
4
Rm
Flt
ch
3
Rm
Flt
ch
2
Rm
Flt
ch
1
Rm
Flt
ch
0
Lo
Flt
ch
7
Lo
Flt
ch
6
Lo
Flt
ch
5
Lo
Flt
ch
4
Lo
Flt
ch
3
Lo
Flt
ch
2
Lo
Flt
ch
1
Lo
Flt
ch
0
10
Diagnostic Status
11
Res
Flg
Module command response
Module response data
Where:
ch = channel
Ovr Alm = Overrange Alarm
Und Alm = Underrange Alarm
Rm Flt = Remote Fault
Lo Flt = Local Fault
Res Flg = Response Flag
Bit
→
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
↓
Write
0
High and Low Error Level
U/D
0-3
Filter Cutoff 0-3
Data Format
Flt
Md
1
High and Low Error Level
U/D
0-3
Filter Cutoff 0-3
Data Format
Flt
Md
2
Cd
Flg
Module command
Module command data
Where:
Out Enbl = Output Enable
U/D = up/down
Flt Md = Fault Module
Cd Flg = Command Flag