Rockwell Automation 1797-OE8 FLEX Ex Analog Modules User Manual User Manual
Page 27

Publication 1797-6.5.1 - May 2005
Understanding Configurable FLEX Ex Analog Module Features 2-11
Table 2.4 1797-OE8 Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
0
mA as
0-20mA
0.1% of
0-20mA
0-22mA
0-22000
(0-22.000mA)
1000
min=0mA
max=22mA
hold
last=hold
50%=11mA
1
% as
0-20mA
0.2% of
0-20mA
0-22mA
0-11000
(0-110.00%)
500
min=0mA
max=22mA
hold
last=hold
50%=11mA
2
0-20mA
0-22mA
not assigned
3
unsigned
integer as
0-20mA
0.03% of
0-20mA
0-20mA
0-65,535
(0-22mA)
3276
min=0mA
max=20mA
hold
last=hold
50%=10mA
4
mA as
4-20mA
0.1% of
4-20mA
2-22mA
2000-22000
(2.000-22.000mA)
1000
min=2mA
max=22mA
hold
last=hold
50%=12mA
5
4-20mA
4-20mA
not assigned
6
4-20mA
4-20mA
not assigned
7
unsigned
integer as
4-20mA
0.03% of
4-20mA
4-20mA
0-65,535
(4-20mA)
4095
min=4mA
max=20mA
hold
last=hold
50%=12mA
8
0-20mA
0-20mA
not assigned
9
0-20mA
0-20mA
not assigned
output =
datatable
(
1,000
)
output = 20
datatable
(
10,000
)
output = 20
datatable
(
65,535
)
output =
datatable
(
1,000
)
output = 16
datatable
(
65,535
)
+ 4