2-12 Understanding Configurable FLEX Ex Analog Module Features
Fault Alarm
Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100Hz (10ms) filter for wire off/lead break detection.
Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.
10
0-20mA
0-20mA
not assigned
11
D/A count
as 0-20mA
0.28% of
0-20mA
0-22mA
0-8000
(0-22mA)
363
min=0mA
max=22mA
hold
last=hold
50%=11mA
12
4-20mA
not assigned
13
% as
4-20mA
0.16% of
4-20mA
3-21mA
-625 - +10625
(2’s complement)
(-6.25% -
+106.25%)
625
min=3mA
max=21mA
hold
last=hold
50%=12mA
14
% as
4-20mA
0.16% of
4-20mA
2-22mA
-1250 - +11250
(2’s complement)
(-12.50% -
+112.50%)
625
min=2mA
max=22mA
hold
last=hold
50%=12mA
15
4-20mA
4-20mA
not assigned
Table 2.4 1797-OE8 Data Formats
Data
Format
Format
Resolution Full
Output
Range
Module Data Processing
Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
output = 22
datatable
(
8,000
)
output = 16
datatable
(
10,000
)
+ 4
output = 16
datatable
(
10,000
)
+ 4