6ć18, Fault dependent group – Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 99
Chapter
Operating in SVĆSuperset Mode
6
6Ć18
FAULT DEPENDENT GROUP associates a set of adapters such that if one
adapter in the group faults, all the other adapters in the group fault, going
to their fail-safe mode of operation. The scanner must be in Program mode
to issue this command. You can specify as many as 8 fault groups.
not used
Byte offset
(Hex)
0202
0204
0206
-021B
021E
Name
021C
00H returned means the command was
successful. Any other value indicates
an error.
12H is both sent and returned.
1 byte per starting group
(4 bytes per adapter)
see Figure 6.8 and Figure 6.9
Bit 7 = semaphore
not used
0220
channel A
control/status
faultĆdependentĆgroup blocks
64 bytes
-025F
not used
channel A
general data
0260
-029F
not used
semaphore
command
confirmation
0203
0205
not used
not used
021D
The VME master processor writes 12 (hex) to the command byte. Then
the VME master processor writes this parameter to the selected channel’s
general data area:
Byte
offset:
Parameter: Description:
0220
fault dependent group block
There are 4 configurable bits for each starting group entry.
An adapter must be in the current scan list to be assigned to a
faultĆdependent group. If you specify an adapter that is not in
the scan list, the scanner writes an illegal configuration error
(16H) to the confirmation status byte. See Figure 6.8
and Figure 6.9.
FAULT DEPENDENT GROUP
command byte 12
description
parameters