Chapter

Installing the Scanner

2

2Ć2

Determine the VMEbus A24/A16 Address Space

Use this diagram and the example to set SW1 and SW2 for the correct
VMEbus address space.

slide switch pushed up

on = closed = 0

1

2

3

4

5

6

7

8

SW1

SW2

slide switch pushed down

off = open = 1

1

2

3

4

5

6

7

8

SW2

A23 A22 A21 A20 A19 A18 A17 A16

SW1

1

2

3

4

5

6

7

8

A15 A14 A13 A12

Important: These pins are

for manufacturing use only

- do not jumper these pins.

reserved

In this VME

operating mode:

these bits:

are valid for this

address space:

SVĆcompatible

A23 through A12

1 channel active

A23 through A13

2 channels active

A15 through A12

1 channel active

A15 through A13

2 channels active

A24

A16

SVĆsuperset

A23 through A13

1 channel active

A23 through A14

2 channels active

A24

If there are switches not accounted for in a particular address space, such as the switches for A16ĆA23

for SVĆcompatible, A16 address space, the switch position does not affect scanner operation.