Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 29
![background image](/manuals/580456/29/background.png)
Chapter
Installing the Scanner
2
2Ć10
Figure 2.1
Make remote I/O connections
To connect the remote I/O cable, do the following:
1. Run the cable (1770ĆCD) from the processor to each
remote I/O adapter in the remote I/O system.
2. Connect the signal conductor with blue insulation to the
3Ćpin connector terminal labeled 1 on the scanner and to
each remote I/O adapter in the remote I/O system.
3. Connect the signal conductor with clear insulation to the
3Ćpin connector terminal labeled 2.
4. Connect the shield drain wire to the middle 3Ćpin
terminal (it is not labeled).
5. Tie wrap the remote I/O network cable to the chassis to
relieve strain on the cable.
6. Terminate the remote I/O link by connecting an external
terminator resistor between the remote I/O terminals
labeled 1 and 2.
To another remote I/O device
Clear
Shield
Blue
82Ć
Ω
or
150Ć
Ω
resistor
Last device on the remote I/O link.
Terminate both ends of a remote I/O link.
1770ĆCD
(Belden 9463)