Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 59
![background image](/manuals/580456/59/background.png)
Chapter
Operating in SVĆCompatible Mode
5
5Ć8
The VME master processor writes 13 (hex) to the command byte. Then
the VME master processor writes these parameters to the first 7 bytes of
the selected channel’s general data area:
Byte
offset:
Parameter: Description:
Byte
offset:
Parameter: Description:
120
I/O link
baud rate
Write one of these values (hex):
01 57.6 kbps (default)
02 115.2 kbps
FF no change
Values 00, 03-FE are reserved. If you write a
reserved value to this field, the scanner writes error
11H in the confirmation status byte.
124
command
complete
interrupt
status ID
The VME master processor writes an 8Ćbit value
here that the scanner will pass to the VME interrupt
handler during the VMEbus interrupt cycle. The
default value is 40H.
121
master
processor
watchdog
timeout
Write one of these values (hex):
00
500 ms (default)
0A-FE
(value x 100) ms (1000-25400ms)
FF
no change
Values 01-09 are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
125
command
complete
interrupt
enable
Write one of these values (hex):
00 generate VMEbus interrupt
upon command completion (default)
01 do not generate VMEbus interrupt
upon command completion
FF no change
Values 02-FE are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
122
master
processor
watchdog
disable
Write one of these values (hex):
01
disable watchdog timer
00,
enable watchdog timer (default)
02-FF
Disable the watchdog timer when you want to run a
master processor application in debug mode without
incurring timeouts that disrupt the application. The
default is debug disabled.
126
SYSFAIL
mask
enable
Write one of these values (hex):
00 SYSFAIL monitor enabled (default)
01 SYSFAIL monitor disabled
FF no change
Values 02-FE are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
123
command
complete
VMEbus
interrupt
level
Write one of these values (hex):
01 level 1
05
level 5
02 level 2
06
level 6
03 level 3
07
level7
04 level 4 (default)
Values outside the range 01-07 are reserved. If
you write a reserved value to this field, the scanner
writes error 11H in the confirmation status byte.
Your code for a SETUP command should include these tasks:
1. get the semaphore
2. set up the general data area
3. send the command interrupt
4. wait for the result
(either poll for confirmation status or wait for an interrupt)
5. clear the semaphore
parameters
coding sequence