Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 90
![background image](/manuals/580456/90/background.png)
Chapter
Operating in SVĆSuperset Mode
6
6Ć9
Byte
offset:
Parameter: Description:
Byte
offset:
Parameter: Description:
0220 I/O link
baud rate
Write one of these values (hex):
01 57.6 kbps (default)
02 115.2 kbps
03 230.4 kbps
FF no change
Values 00, 04-FE are reserved. If you write a
reserved value to this field, the scanner writes error
11H in the confirmation status byte.
0226 SYSFAIL
monitor
enable
Write one of these values (hex):
00 SYSFAIL monitor enabled (default)
01 SYSFAIL monitor disabled
FF no change
Values 02-FE are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
0221 master
processor
watchdog
timeout
Write one of these values (hex):
00
500 ms (default)
0A-FE
(value x 100) ms (1000-25400ms)
FF
no change
Values 01-09 are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
0227 input image
table
monitor
interrupt
level
Write one of these values (hex):
01 level 1
05
level 5
02 level 2
06
level 6
03 level 3
07
level7
04 level 4 (default)
Values outside the range 01-07 are reserved. If
you write a reserved value to this field, the scanner
writes error 11H in the confirmation status byte.
0222 master
processor
watchdog
disable
Write one of these values (hex):
01
disable watchdog timer
00,
enable watchdog timer (default)
02-FF
Disable the watchdog timer when you want to run a
master processor application in debug mode without
incurring timeouts that disrupt the application. The
default is debug disabled.
0228 input image
table
monitor
interrupt
status ID
The VME master processor writes an 8Ćbit value
here that the scanner will pass to the VME interrupt
handler in response to an input image table monitor
interrupt. The default value is 42H.
0223 command
complete
interrupt
level
Write one of these values (hex):
01 level 1
05
level 5
02 level 2
06
level 6
03 level 3
07
level7
04 level 4 (default)
Values outside the range 01-07 are reserved. If
you write a reserved value to this field, the scanner
writes error 11H in the confirmation status byte.
0229 input image
table
monitor
enable
Write one of these values (hex):
00 input image table monitor enabled
01 input image table monitor disabled (default)
FF no change
Values 02-FE are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
0224 command
complete
interrupt
status ID
The VME master processor writes an 8Ćbit value
here that the scanner will pass to the VME interrupt
handler during the VMEbus interrupt cycle. The
default value is 40H.
022A input image
table low
bound
The low bound sets one boundary for a contiguous
segment of the input image table that the scanner
monitors for a change. The default low bound is
rack 0, group 0. Legal values are 00H to the high
bound.
Values greater than the high bound result in error
11H in the confirmation status byte.
0225 command
complete
interrupt
enable
Write one of these values (hex):
00 generate VMEbus interrupt
upon command completion (default)
01 do not generate VMEbus interrupt
upon command completion
FF no change
Values 02-FE are reserved. If you write a reserved
value to this field, the scanner writes error 11H in
the confirmation status byte.
022B input image
table high
bound
The high bound sets one boundary for a contiguous
segment of the input image table that the scanner
monitors for a change. The default high bound is
rack 15, group 7. Legal values are from the low
bound to 7EH.
Values between 80-FF (hex) and values less than
the low bound result in error 11H in the confirmation
status byte.