Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 177
Troubelshooting
Chapter 9
9Ć3
Code
(hex):
Corrective Action:
Significance:
14
Block transfer queue full. The VME master processor
issued a block transfer command when the scanner's
block transfer queue was full.
Wait for one or more of the block transfers already in
the scanner's queue to finish, then reĆissue
the command.
15
Invalid length of data. The VME master processor
specified a length that cannot be used for the
command issued.
Specify a proper length.
16
Illegal configuration. The VME master processor
issued a:
•
SCAN LIST command that deletes an adapter listed
in a FAULT DEPENDENT GROUP.
•
command placing an adapter not in the scan list into
a FAULT DEPENDENT GROUP.
1. Adjust the fault dependent group and then reĆissue
the scan list.
2. Adjust the scan list and the reĆissue the fault
dependent group command.
23
Block transfer timeout. A block transfer specified by
the BT tag did not complete within 4 seconds and
was aborted.
1. Make sure a block transfer module is in the
slot specified.
2. Make sure the chassis holding the module is
turned on.
3. Make sure the adapter is in the scan list.
4. Make sure the scanner is not in the program mode.
5. Check the length of data value to make sure it
matches the module, or make the value zero.
6. Check the manual for the module in use.
25-2E
30-43
I/O link error. A failure occurred in the transfer of
information between the I/O module and the scanner.
An application program cannot cause these errors,
because they are associated with the communication
protocol on the I/O link.
1. Check the block transfer hardware configuration.
2. Eliminate electrical noise that may interfere with
remote I/O communication.
3. Use 57.6 kbps instead of 115.2 kpbs.
4. Ensure proper grounding of your I/O racks.
5. Consult the factory and/or replace the block
transfer module.
6. An error occurred within the scanner. Try cycling
power before removing the scanner.
2F
Block transfer accepted. The block transfer was
accepted by the scanner and is now in the
scanner's queue.
none