Rockwell Automation 6008-SV2R VMEbus remote I/O Scanner User Manual
Page 107
![background image](/manuals/580456/107/background.png)
Chapter
Operating in SVĆSuperset Mode
6
6Ć26
Format item:
Description:
Format item:
Description:
in scan list
bit 12
Contains one of these values:
1
adapter is in the current scan list
0
adapter not in current scan list
group faulted
bit 7
Contains one of these values:
1
fault exists in the fault dependent group
associated with the adapter
0
no fault exists in the fault dependent
group associated with the adapter
adapter attached
bit 11
Contains one of these values:
1
adapter resides at this address
0
no adapter resides at this address
line status
bit 6-4
Contains one of these values (hex):
000
adapter is off line
any other
adapter is on line
value
valid configuration
bit 10
Contains one of these values:
1
adapter type, size, and address are valid
0
adapter type, size, and/or address not
valid; adapter is improperly configured
in fault dependent
group
bit 3
Contains one of these values:
1
adapter is in the fault dependent group
identified by the fault dependent group
number (bits 2-0)
0
adapter is not in a fault dependent group
adapter size
bits 9-8
Contains one of these values (hex):
00
1/4 rack addressing
01
1/2 rack addressing
10
3/4 rack addressing
11
full rack addressing
fault dependent
group number
bits 2-0
The value (0-7 binary) identifies the fault
dependent group to which this adapter belongs.
Figure 6.12
Format for one entry in the scan list
6
5
4
3
2
1
0
7
Format item:
Description:
rack number
bits 5-2
The value (0-15 binary) identifies the rack number.
starting I/O group number
bits 1-0
One of the following values identifies the starting I/O group:
00
group 0
01
group 2
10
group 4
11
group 6