AutoMax Programming Executive Version 3.x
no SSRT was selected, enter the name of the SSRT you want to fetch. If
you are fetching at the task level, you must enter the task name with its
extension. See the figure below.
Step 3. The dialog box contains two option buttons. If you want to fetch the
latest version of the SSRT, select the Latest Version" button. If you want
to see a list of the previous snapshots from which you can choose the
version of SSRT, select the See List of Snapshots" button.
Step 4. The dialog box has a check box for fetching tokens from the Version
Control Library. Select this box if you want to fetch all the tokens held by
the VCL (within the scope of the fetch) to the AutoMax library. Note that
the check box will not appear if tokens are not enabled or if you are
fetching at the task level.
Step 5. Select OK to begin the fetch operation or Cancel to return to the System
Configurator (or the Task Manager).
If you selected OK, a dialog box may be displayed that indicates that certain
racks are being prepared. This means that the AutoĆ
Max directories for the racks within the scope of the fetch operation are being
emptied of all their AutoMax files. If the directory contains nonĆAutoMax files, they
will remain in the directory. If the directory is empty, it will be deleted. The fetch
operation will reĆbuild the AutoMax rack directories with the files contained in the
version of the SSRT being fetched. For example, if an AutoMax system contains a
section with three racks, and you fetch a version of that section that contains only
two racks, the third rack and all its associated task files will be gone.
When empty directories have been deleted, a dialog box will be displayed that
shows what SSRT is being processed. When processing is complete, a diagram
will be displayed that shows the percentage of the fetch operation that has been
completed. When the retrieval of files is complete, you will return to Windows,
where a dialog box labeled Rebuilding Databases will be displayed. After the
AutoMax databases are rebuilt, a FETCH COMPLETE" message will appear. You
will then return to the same place you were before the fetch operation (System
Configurator or Task Manager).