Rockwell Automation 57C620 AutoMax Programming Executive Version 3.8 User Manual
Page 145
9Ć3
System Security
Table 9.1 Ć Accessing PasswordĆProtected Features
Rack Power
Supply KeyĆ
switch Position
Any
PosiĆ
tion
PROĆ
TECT
SETUP
PROGRAM
User's Access
Level
None
Any
level Data Task Rack Data Task Rack
Action
Force Common
No
No
No
No
No
Yes
Yes
Yes
Force Local
No
No
No
No
No
No
Yes
Yes
Force I/O
No
No
No
No
No
Yes
Yes
Yes
Set Common
No
No
No
No
No
Yes
Yes
Yes
Set Local
No
No
No
No
No
No
Yes
Yes
Set I/O
No
No
No
No
No
Yes
Yes
Yes
Set/Tune Tunable
No
No
No
Yes
Yes
No
Yes
Yes
Load Normal
Config
No
No
No
No
No
No
No
Yes
Load Debug
Config
No
No
No
No
No
No
No
Yes
Load Single POB
File
No
No
No
No
No
No
Yes
1
Yes
Load Single Task
No
No
No
No
No
No
2
Yes
Yes
Delete Task
No
No
No
No
No
No
Yes
Yes
Start Task
No
No
No
No
No
No
Yes
Yes
Stop NonĆCritical
Task
No
No
No
No
No
No
Yes
Yes
Save Task from
Rack
No
Yes
3
No
Yes
Yes
No
Yes
Yes
Load All POB
Files
No
No
No
No
No
No
Yes
Yes
Load All
No
No
No
No
No
No
No
Yes
Delete All Tasks
No
No
No
No
No
No
Yes
4
Yes
Start All Tasks
No
No
No
No
No
No
Yes
4
Yes
Stop All Tasks
No
No
No
No
No
No
Yes
4
Yes
Load AutoMax
OS
No
No
No
No
No
No
No
Yes
Load Single UDC
OS
No
No
No
No
No
No
Yes
1
Yes
Load All UDC OS
No
No
No
No
No
No
Yes
1
Yes
Modify PC Task
No
No
No
No
No
No
Yes
Yes
Auto Run
No
No
No
No
No
Yes
Yes
Yes
Monitor
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Notes: A user with privileged access may relinquish this privilege by
timing out after two minutes offline, or by selecting to relinquish
access online. Functions not listed in the table do not require
privileged access.
(notes continued on next page)